EWS-102 CONTROL UNIT MULTI ANALOG
Analog output Selec on
OUT
There are seven selectable output ranges available. To view the current value press
scroll through output types. Select and save required option by pressing
4-20
Output type 4-20mA.
0-20
Output type 0-20mA.
0-24
Output type 0-20mA.
0-5
Output type 0-5V.
bi 5
Output type +/-5V
bi10
Output type +/-10V
P
CODE
ERR1
Sensor Signal Input - Negative
Err2
Insufficient Sensor Signal
Err3
Sensor Offset Too High - Positive
Err4
Sensor Offset Too High - Negative
Err5
Trying to calibrate without Control Signal link
Err6
Sensor not connected to EWS
Firmware 5.5 Rev 1 s
e
a era i
4mA = no load, 20mA = full load
0mA = no load, 20mA = full load
0mA = no load, 24mA = full load
0V = no load, +5V = full load
-5V = no load, 0v + half load, +5V = full load
-10V = no load, 0v + half load, +10V = full load
ERROR
.
CAUSE/SOLUTION
Reverse connection of sensor signal leads
Installation Error - Contact Garan
Installation Error - Contact Garan
Installation Error - Contact Garan
Fit link between control signal terminals
Connect sensor/check sensor wiring
www.garan.co.uk
SYSTEM SETUP
then use
to
ERROR CODES
Page 4