E-T-A ESX10-TB-102 Manual - Page 10
Browse online or download pdf Manual for Protection Device E-T-A ESX10-TB-102. E-T-A ESX10-TB-102 15 pages. Electronic circuit protector
Electronic Circuit Protector ESX10-T.-DC 24 V - Installation guidelines and safety instructions
Mounting examples for ESX10-T
insert signal
bars to be flush with
housing and place them
centrally over the contacts
4
5 ESX10-TA
with busbars
Description of installation:
With a block of devices the busbars have to be inserted before wiring.
Max. 10 plug-in cycles for busbars allowed.
Recommendation:
The line entry busbars and signal busbars should be interrupted after 10 devices and line entry should start anew.
Table of busbar lengths
(X 222 611 02 and X 222 005 03 or their cut lengths - see accessories)
Number of devices
Length of rail
[mm] ± 0,5 mm
10
LINE+ busbar
X22261102 grey
signal bar
X22200503 grey
or
jumper
X22200513 grey
remove protection against
brush contact from bottom side
insert busbars
and protection slides
to be flush with housing sides
5 ESX10-TB
with busbars
and jumpers
2
3
22
34.5
47
continuous busbar
500 mm length, cut
0 V busbar
X22261102 grey
4
5
6
59.5
72
www.e-t-a.de
(12.5 x n)-3 = length of busbars ± 0.5
e. g. (12.5 x 5)-3 = 59.5 ± 0.5
insert protection against
brush contact
12.5 x n = width of protector block
e. g. 12.5 x 5 = 62.5
5 ESX10-TD
with busbars
7
8
9
84.5
97
109.5
10
122
1822