Alish AM5H-A User Manual - Page 5

Browse online or download pdf User Manual for Measuring Instruments Alish AM5H-A. Alish AM5H-A 5 pages. 5 digital micro-process meter with 2~4 alarms / analog output / rs-485

Modbus RTU Mode Protocol Address Table

Data: 16Bit / 32Bit, +/- is 8000~7FFF (-32768~32767), 80000000~7FFFFFFF(-2147483648~2147483647)
Modbus HEX
Name
40001
0000
ID
Model number identification; AM5H-A is "00"
Current alarm output & external control input status display; range: 0000~00FE
(0~254) (0:OFF, 1:ON) (Bit7:AL4, Bit6: AL3, Bit5: AL2, Bit4: AL1, Bit3:HD,
40002
0001
STATUS
Bit2:MAX, Bit1:AZ)
Parameters setting; range: 0000~00FF (0~255) Bit0~3: ACT1~4 (0:HI, 1:LO),
0002
FUNC
40003
Bit4:CON, Bit5:POLAR
0003
Decimal point setting; range: 0000~0004 (0~4) 0:10, 1:10, 2:10, 3:10, 4:10
40004
DP
40005
0004
BAUD
Baud rate setting; range: 0000~0003 (0~3) 0:38400, 1:19200, 2:9600, 3:4800
40006
0005
Parity setting; range: 0000~0003 (0~3), 0:N.8.2., 1:N.8.1., 2:EVEN, 3:ODD
PARI
40007
0006
Display average setting; range: 0001~0063 (1~99)
AVG
0007
LCUT
Display low cut setting; range: 0000~0063 (0~99)
40008
ADDR
40009
0008
Address setting; range: 0000~00FF (0~255)
Alarm 1 act delay time setting; range: 0000~0063 (0~99)
40010
0009
DEL1
Alarm 2 act delay time setting; range: 0000~0063 (0~99)
40011
000A
DEL2
Alarm 3 act delay time setting; range: 0000~0063 (0~99)
40012
000B
DEL3
40013
000C
Alarm 4 act delay time setting; range: 0000~0063 (0~99)
DEL4
SB
40014
000D
Alarm start band setting; range: FF9D~0063 (-99~99)
40015
000E
Alarm start delay time setting; range: 0000~0063 (0~99)
SDT
Alarm 1 hysteresis setting; range: 0000~270F (0~9999)
000F
HYS1
40016
0010
Alarm 2 hysteresis setting; range: 0000~270F (0~9999)
40017
HYS2
0011
Alarm 3 hysteresis setting; range: 0000~270F (0~9999)
40018
HYS3
0012
Alarm 4 hysteresis setting; range: 0000~270F (0~9999)
40019
HYS4
0013
Pass code setting; range: 0000~4E1F (0~19999)
40020
CODE
Analog output zero setting; range: D8F1~270F (-9999~9999)
40021
0014
AZERO
40022
0015
Analog output span setting; range: D8F1~270F (-9999~9999)
ASPAN
40023
0016
DSPL
Display low scale setting; range: FFFFB1E1~0001869F(-19999~99999) Hi Bit
0017
Display low scale setting; range: FFFFB1E1~0001869F(-19999~99999) Low Bit
40024
0018
40025
DSPH
Display hi scale setting; range: FFFFB1E1~0001869F(-19999~99999) Hi Bit
Display hi scale setting; range: FFFFB1E1~0001869F(-19999~99999) Low Bit
40026
0019
AL1
Alarm 1 setpoint setting; range: FFFFB1E1~0001869F(-19999~99999) Hi Bit
40027
001A
Alarm 1 setpoint setting; range: FFFFB1E1~0001869F(-19999~99999) Low Bit
40028
001B
40029
001C
AL2
Alarm 2 setpoint setting; range: FFFFB1E1~0001869F(-19999~99999) Hi Bit
40030
001D
Alarm 2 setpoint setting; range: FFFFB1E1~0001869F(-19999~99999) Low Bit
001E
Alarm 3 setpoint setting; range: FFFFB1E1~0001869F(-19999~99999) Hi Bit
40031
AL3
001F
Alarm 3 setpoint setting; range: FFFFB1E1~0001869F(-19999~99999) Low Bit
40032
0020
AL4
Alarm 4 setpoint setting; range: FFFFB1E1~0001869F(-19999~99999) Hi Bit
40033
0021
40034
Alarm 4 setpoint setting; range: FFFFB1E1~0001869F(-19999~99999) Low Bit
AM5H-A
Descriptions
0
-1
-2
-3
-4
P5
Modbus HEX
Name
40035 0022
ANLO
40036 0023
Act
40037 0024
ANHI
R
40038
0025
R
40039
0026
DISPLAY
40040
0027
0028
INLO
R/W
40041
40042
0029
R/W
40043
002A
INHI
R/W
40044
002B
R/W
40045
002C
MAX
R/W
002D
40046
R/W
40047
002E
HOLD
R/W
40048
002F
R/W
40049
0030
AZ
R/W
40050
0031
R/W
R/W

CALIBRATION OPERATING PROCEDURES

R/W
Display
R/W
R/W
R/W
Measuring Status
Press
E
+
for 3s
R/W
Input Low Scale
R/W
Calibration (inLo)
Press
E
R/W
Input Hi Scale
R/W
Calibration (inHi)
Press
E
R/W
System Setting
R/W
Page(SYS)
+
R/W
R/W
Warning: Calibration of this meter requires a standard signal with 0.01%
R/W
accuracy or better and an external meter with 0.005% accuracy
or better.
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
AM5H-A
Descriptions
Analog output low scale setting; range: FFFFB1E1~0001869F (-19999~99999) Hi Bit
Analog output low scale setting; range: FFFFB1E1~0001869F (-19999~99999) Low Bit
Analog output hi scale setting; range: FFFFB1E1~0001869F (-19999~99999) Hi Bit
Analog output hi scale setting; range: FFFFB1E1~0001869F (-19999~99999) Low Bit
Current display; range: FFFFB1E1~0001869F (-19999~99999) Hi Bit
Current display; range: FFFFB1E1~0001869F (-19999~99999) Low Bit
Input low calibrated value display; range: 00029F16~004EA4A8 (171798~5153960) Hi Bit
Input low calibrated value display; range: 00029F16~004EA4A8 (171798~5153960) Low Bit
Input hi calibrated value display; range: 00029F16~004EA4A8 (171798~5153960) Hi Bit
Input hi calibrated value display; range: 00029F16~004EA4A8 (171798~5153960) Low Bit
Max. hold display; range: FFFFB1E1~0001869F (-19999~99999) Hi Bit
Max. hold display; range: FFFFB1E1~0001869F (-19999~99999) Low Bit
Data hold display; range: FFFFB1E1~0001869F (-19999~99999) Hi Bit
Data hold display; range: FFFFB1E1~0001869F (-19999~99999) Low Bit
Auto zero; range: FFFFB1E1~0001869F (-19999~99999) Hi Bit
Auto zero; range: FFFFB1E1~0001869F (-19999~99999) Low Bit
Descriptions
Calibration
Calibration operating procedures.
1. Input standard low scale signal.
2. Press
to calibrate input low scale.
E
1. Input standard hi scale signal.
2. Press
to calibrate input hi scale.
E
1. Finish calibration operating procedures will enter to
system setting group.
2.Press
to back to measuring status.
P6
Act
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
Default