Consult the technical table for the proper ring (38) distance. (Rings are counted from the gas safety
device).
-
Check the gas supply for the proper gas pressure and gas type and do a leakage test first.
-
Take the heater into operation and do a visual examination of the flame as explained above.
End-of life disposal
The infrared heaters are made up of valuable recyclable materials. Therefore, deliver your heater at the
end of its life in a recycling company.

Fault finding table

Trouble
Burner does not light.
Burner does not light.
Spark is available
Burner does not light.
No spark available
Burner extinguishes after
lighting
Flames leave the
- confines of the burner
- or are sooting
- or a blue cloud is under
the reflector
Version: Sept 2017
Action
Check if gas valve of the gas cylinder or gas line is open
Check if gas cylinder is empty
Purge air out of the new gas lines
First ignition will take up to 60 or more seconds before gas is available
Check if the injector is blocked
Check if the gas pressure/gas quality is identical to the pressure
indicated on the data plate
Check if the burner is on high fire setting
Check if during sparking ignition is possible manually with a BBQ
lighter
Location of the ignitor tip to the inner burner is incorrect.
Check if the gas safety device opens. Click can be heard when
opening. If not, coil EID2G is broken
Check if there is 230 Volt available at the EID2G
Spark electrode not connected to the EID2G
Spark electrode gap incorrect. Shall be between 3-4 mm
Spark jumps off to other metal parts before the spark electrode. Check
wire, connectors and ignitor ceramics. Check if parts are dry
Ignition loop is not complete. Check the ignition and earthing wire
Ignitor EID2G is broken. Replace
EID2G in recovery phase. Leave the EID2G connected to 230V for 20
minutes to reset and try again
Keep button safety device pressed for a longer period (up till 25
seconds)
Check the position of the thermocouple (see above)
Check if the thermocouple nut is connected properly to the gas safety
device and to the EID2G unit and that the nuts are not loose
Check if the thermocouple has the proper depth in the burner,
measured on the top plate (Global 5 = 25mm, Global 10 = 22 mm)
Thermocouple switch in EID2G is broken. Check (after switching 230V
to the EID2G) by multimeter if resistance of the internal switch is <25
Thermocouple or magnetic coil of the safety device is broken.
Gas pressure lower than minimum requested
Heater not suspended at 15 degrees angle
Gas pressure is too high. Check the gas pressure with the data plate
Check if the gas pressure regulator is broken.
Wrong gas is used. Check data plate for the correct gas supply
Venturi/air inlet is blocked/dirty
Valve dual injection model (Di) is leaking
Check the size of the venturi and injector with the table
Not enough fresh air available due to mounting situation
Air filter is dirty
Heater not suspended at 15 degrees angle
Small o-ring (33) (Di) is missing or leaking
13