4.3.2. Multiple outdoor unit installation
• Provide at least 9/16in. (15mm) of space between the outdoor units if multiple units are
installed.
• When routing the piping from the side of an outdoor unit, provide space for the piping.
• No more than 3 units must be installed side by side. When 3 units or more are
arranged in a line, provide the space as shown in the following example when an
obstruction is present also in the upward area.
When the upward area is open (Unit : in. (mm))
(1) Obstacles at rear only
11-13/16
(300) or more
(3) Obstacles at front and rear only
When an obstruction is present also in the upward area (Unit : in. (mm))
Obstacles at rear and above only
Max. 11-13/16 (300)
59-1/16 (1500)
or more
4.3.3. Outdoor units installation in multi row (Unit : in. (mm))
(1) Single parallel unit arrangement
39-3/8 (1000) or more
(2) Multiple parallel unit arrangement
En-6
(2) Obstacles at front only
19-11/16 (500) or more
59-1/16 (1500) or more
59-1/16 (1500)
or more
19-11/16 (500)
or more
5-29/32 (150) or more
78-3/4 (2000) or more
23-5/8 (600) or more
19-11/16 (500) or more
118-1/8 (3000) or more
23-5/8 (600) or more
59-1/16 (1500) or more
4.4. Transporting the unit
Do not touch the fins.
Otherwise, personal injury could result.
When carrying the unit, hold the handles on the right and left sides and be careful.
If the outdoor unit is carried from the bottom, hands or fingers may be pinched.
• Carry slowly in the manner as shown on "Fig. B" holding the handles "Fig. A" in right
and left sides. (Be careful not to touch with hands or objects.)
• Be sure to hold the handles on the sides of the unit. Otherwise, the suction grilles on
the sides of the unit may be deformed.
5-29/32 (150)
Fig. A
or more
Fig. B
4.5. Installation
(Unit : in. (mm))
• Install 4 anchor bolts at the locations indicated with arrows in the above figure.
• To reduce vibration, do not install the unit directly on the ground. Install it on a secure
base (such as concrete blocks).
• The foundation shall support the legs of the unit and have a width of 1in. (50mm) or more.
• Depending on the installation conditions, the outdoor unit may spread its vibration
during operation, which may cause noise and vibration. Therefore, attach damping
materials (such as damping pads) to the outdoor unit during installation.
• Install the foundation, making sure that there is enough space for installing the
connection pipes.
• Secure the unit to a solid block using foundation bolts. (Use 4 sets of commercially
available M10 bolts, nuts, and washers.)
• The bolts should protrude 25/32 in. (20 mm).
(Refer to the figure below.)
• If overturning prevention is required, purchase the necessary commercially available
items.
Fix securely with bolts on a solid block. (Use 4 sets of commercially available M10 bolt,
nut and washer.)
WARNING
CAUTION
Suction grille
Handle
Suction grille
Front view
Rear view
5-3/16
25-19/32
(132)
(650)
1-31/32
AIR
(50)
Handle
4-11/16
(119)
1-31/32
(50)
4 - Φ 12 Hole
Bolt
Nut
Base