8.3. Group control system
• When setting rotary switch, do not touch any other parts on the circuit board directly
with your bare hands.
• Be sure to turn off the main power.
A number of indoor units can be operated at the same time using a single remote control-
ler.
(1) Wiring method (indoor unit to remote controller)
Indoor unit 0
Indoor unit 1
1 2 3
1 2 3
1
2 3
R W B
Remote
controller cable
Remote controller
When ground wire is necessary
(2) Rotary switch setting (indoor unit)
Set the unit number of each indoor unit using the rotary switch on the indoor unit circuit
board.
The rotary switch is normally set to 0.
Rotary Switch
NOTE
Be sure to set the unit numbers sequentially.
(3) Remote controller setting
1. Turn on all of the indoor units.
* Turn on the indoor unit with the unit number 00 last. (Within 1 minute)
2. Set the refrigerant circuit address. (Assign the same number to all of the indoor units
connected to an outdoor unit.)
Function Number
Refrigerant circuit
address
3. Set the "primary" and "secondary" settings. (Set the indoor unit that is connected to
the outdoor unit using a transmission cable as the "primary".)
Function Number
Primary
Secondary
4. After completing the function settings, turn off all of the indoor units, and then turn
them back on.
* If error code 21, 22, 24, or 27 is displayed, there may be an incorrect setting.
Perform the remote controller setting again.
NOTE
• When different indoor unit models are connected using the group control system, some
functions may no longer be available.
• If the group control system contains multiple units that are operated simultaneously, con-
nect and set the units as shown below.
• Auto-changeover operates under the same mode with model unit number 00.
• It should not be connected to any other Gr that is not of the same series (A**G only).
En-12
9379123037-02.indb 12
9379123037-02.indb 12
CAUTION
Indoor unit 2
Indoor unit 3
1 2 3
1 2 3
Bus wire
Indoor unit
Setting Value
02
00~15
Setting Value
00
51
01
Standard
Simultaneous
pair
Outdoor
Outdoor
unit 1
unit 2
Indoor
Indoor
Remote
controller
unit
unit
Rotary switch setting
00
01
(unit number)
Remote controller
setting
00
01
Refrigerant circuit
address
00
00
Primary/Secondary
: Transmission cable, Power supply cable
: Remote controller cable
* Make sure that the indoor unit with the unit number 00 is connected to the outdoor unit
using a transmission cable.
8.4. Dual remote controllers
• Two separate remote controllers can be used to operate the indoor units.
• The timer and self-diagnosis functions cannot be used on the secondary units.
(1) Wiring method (indoor unit to remote controller)
Indoor unit
1 2 3
When ground wire
is necessary
1 2 3
R W B
Primary unit
Remote controller
(2) Remote controller DIP switch 1 setting
Set the remote controller DIP switch 1 No. 2 according to the following table.
(Refer to 7.2. Setting the dip switches)
Primary unit
Number of remote
controllers
DIP SW 1 No. 2
1 (Normal)
OFF
2 (Dual)
OFF
Simultaneous
twin
triple
Outdoor
unit 3
Indoor
Indoor
Indoor
Indoor
unit
unit
unit
unit
02
03
04
05
01
02
02
02
01
00
01
01
: Power supply cable
: Bus wire
Remote controller cable
1 2 3
R W B
Secondary
unit
Secondary unit
DIP SW 1 No. 2
–
ON