Fujitsu ABYG30LRTE Design & Technical Manual - Page 47

Browse online or download pdf Design & Technical Manual for Air Conditioner Fujitsu ABYG30LRTE. Fujitsu ABYG30LRTE 47 pages. Split type ceiling type (50hz) indoor unit outdoor unit
Also for Fujitsu ABYG30LRTE: Service Manual (28 pages)

Fujitsu ABYG30LRTE Design & Technical Manual
10.

SAFETY DEVICES

Circuit protection
Fan motor protection
High pressure protection
Compressor protection
Protection form
Current fuse (Near the terminal)
Current fuse (Filter printed circuit board)
Current fuse (Main printed circuit board)
Thermal protection program
Pressure switch
Thermal protection program (Compressor temp.)
Thermal protection program (Discharge temp.)
- (02 - 12) -
Model
AO  G30LETL
AO  G36LETL
250V 25A
250V 10A
250V 3.15A
OFF : 140±20°C
ON : 110±20°C
OFF : 4.2±0.1MPa
ON : 3.2±0.15MPa
OFF : 120°C
ON : 80°C
OFF : 110°C
ON : After 7 minutes