Chapter 2 LT260 Installation
2.2 Installation Area
2.2.2

Notes of Mounting in the Rack

The rack must be a 19 inch rack and meet the EIA standard universal pitch.
The dimension of the prop for fixing the rack must meet
The dimensions of the protruding objects such as props in the rack must meet
The hole geometries of the props must be 9.5 mm or larger corner holes, 9mm corner holes, or 6.8mm
round holes.
There must be a vent hole in the anteroposterior position and the library must be coolable enough.
(The temperature in the rack not to exceed the limited temperature. Refer to "Operating" under "Tempera-
ture" in
Table 2.1
Take measures to ensure the physical stability of the entire rack (including the pulled out status of
modules from a rack). If the rack is equipped with the anti-toppling feature, be sure to use it. Also, mount
the LT260 in the lowest location possible. If the LT260 is mounted in combination with other devices,
heavier devices must be mounted in the lower locations. If the LT260 is mounted together with other
devices the total height of this library and other devices must be under 24U.

Figure 2.2 Explanation drawing of the dimensions (top view)

Props of the rack
 
Front
Front door
FUJITSU Storage ETERNUS LT260 Tape Library User's Guide -Site Planning-
for details.)
Inside dimension
36mm
893mm
20
Copyright 2018 FUJITSU LIMITED
Figure 2.2
and
Figure
2.3.
Figure 2.2
662~783mm
Protruding objects
ETERNUS LT260
Space for cables
60mm or larger
and
Figure
2.3.
Rack rails
Props of the rack
Rear door
P3AM-8782-06ENZ0