Kohler 10RESV Installation Manual - Page 13

Browse online or download pdf Installation Manual for Portable Generator Kohler 10RESV. Kohler 10RESV 48 pages. Residential/commercial generator sets
Also for Kohler 10RESV: Installation Instructions (2 pages)

Kohler 10RESV Installation Manual
Genset Model
Spec Number
Serial Number
Material Number
Service Duty
Alt Model
Insulation
MFG Date
1. Specification
Number
Figure 1-2 Name Plate
1.4.1

Mounting Area

The generator set is shipped on a wooden pallet.
Remove the wooden pallet before positioning the
generator set. Prepare a flat, level mounting area
covered with a weed barrier and gravel or a concrete
mounting pad. Set the generator set directly on the
gravel or concrete.
Note: When installing a concrete mounting pad, the
generator set must be secured to the mounting
pad to prevent shifting or movement caused by
engine
vibration.
GM92228-KP1-QS and GM92228-KP2-QS, use
the screw inserts in the mounting pad to secure
the generator set. See TT--1619 for concrete
mounting pad installation instructions.
Do not install the generator set directly on grass, wood,
or other combustible materials. Clear all combustible
materials, including plants and shrubs, building
materials, and lawn furniture, from an area at least 1.2 m
(4 ft.) beyond the exhaust end of the generator set. See
the dimension drawing in Section 3.
TP-6984
5/17a
8RESV-SA1
GM88347-GA7
XXXXXXXX
XXXXXXXX
29
STANDBY
Amps
kW
7.00
240
Voltage
Phase
1
7.00
kVA
2F3
3600
1.0
RPM
PF
H
12V
60
Battery
Hz
07/31/2015
NAT GAS
Fuel
For
mounting
1.4.2

Exhaust Requirements

1
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Servicing the exhaust system.
severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely
hot during operation.
Figure 1-3 gives the exhaust temperature at rated load.
Mount the generator set so that the hot exhaust does not
blow on plants or other combustible materials. Maintain
the clearances shown in the dimension drawing in
Section 3.
Exhaust
Exhaust gas exiting the
enclosure at rated kW,
_C (_F)
Figure 1-3 Exhaust Flow and Temperature
The generator set requires correct air flow for cooling
pads
and combustion. The inlet and outlet openings in the
sound enclosure provide the cooling and combustion
air. Figure 1-4 shows the locations of the cooling air
intake and exhaust vents. Inspect the air inlet and outlet
openings inside and outside the housing to ensure that
the air flow is not blocked.
1
1. Air intake
2. Exhaust outlet
Figure 1-4 Cooling Air Intake and Exhaust
WARNING
Hot parts can cause
Temperature,
Model
_C (_F)
8RESV(L)
190 (374)
10/12RESV(L)
106 (224)
FRONT VIEW
Section 1 Installation
2
tp6879
13