Kohler 13ERG Operation Manual - Page 19
Browse online or download pdf Operation Manual for Portable Generator Kohler 13ERG. Kohler 13ERG 48 pages. Commercial mobile generator set
2.4.5
Resetting the Controller after a
Fault Shutdown
Always identify and correct the cause of a fault
shutdown before resetting the controller.
following procedure to reset the generator set controller
after a fault shutdown.
1. Move the generator set master switch to the
OFF/RESET position.
2. Disconnect the generator set from the load using
the line circuit breaker or ATS. See the safety
precautions at the beginning of this manual before
proceeding.
3. Identify and correct the cause of the fault
shutdown.
See the safety precautions at the
beginning of this manual before proceeding. Refer
to Section 4, Troubleshooting.
4. Start the generator set by moving the generator set
master switch to RUN. Test operate the generator
set to verify that the cause of the shutdown has
been corrected.
5. Shut the generator off by moving the generator set
master switch to the OFF/RESET position.
6. Reconnect the generator set to the load using the
line circuit breaker or ATS.
7. Move the generator set master switch to the AUTO
position for startup by remote transfer switch,
remote start/stop switch, or remote digital gauge.
Opening and closing the remote start/stop contact
also resets the controller.
2.4.6
Continuous Power Mode
The controller is powered by the generator set engine
starting battery. A jumper on the back of the controller
maintains power to the controller at all times.
Controllers are shipped with the jumper connected.
Note: Remote communications require an active
(powered-up) controller.
ADC 2100 consumes 250 mA when the master
switch is in the AUTO position with the jumper
connected.
If you do not plan to use your
generator set for a long period of time, Kohler
recommends moving the master switch to the
OFF/RESET position (0 mA draw).
Disconnecting the jumper allows the controller to power
down automatically 48 hours after the generator set
shuts down if the generator set master switch is in the
TP-6334
9/04
Use the
Be advised that the
AUTO position. A remote start signal (from a transfer
switch or a remote start/stop switch connected to P21
connector, leads 3 and 4) or moving the generator set
master switch to the RUN position turns the controller
back on. See the Installation Manual for instructions to
disconnect the jumper.
Note: For remote starting using the digital gauge, the
continuous power mode jumper must be
connected.
2.5 Circuit Protection
If the generator set circuit breaker trips or the fuses blow
repeatedly, see Section 4, Troubleshooting, for possible
causes.
2.5.1
Line Circuit Breaker
A line circuit breaker interrupts the generator output in
the event of a fault in the wiring between the generator
and the load. The line circuit breaker location is shown
in Figure 1-1. If the circuit breaker trips, reduce the load
and switch the breaker back to the ON position.
2.5.2
Fuses
The engine harness contains three 10-amp inline fuses.
Always identify and correct the cause of a blown fuse
before restarting the generator set. Refer to section 4,
Troubleshooting, for conditions that may indicate a
blown fuse.
Obtain service from an authorized
distributor/dealer.
Controller Fuse. A replaceable 10-amp fuse protects
the controller circuitry. If the controller display is dark,
check the battery and battery connections and then
check the controller fuse. Replace the fuse if it is blown.
Relay Fuse. A replaceable 10-amp fuse protects the
engine relays. If the generator set does not crank, check
the battery and battery connections and then check the
relay fuse. Replace the fuse if it is blown.
Auxiliary Winding Fuse. A replaceable 10-amp fuse
protects the alternator.
Fuse
Label
Auxiliary Winding
F1
Relay Interface
F2
Board
Controller
F3
Figure 2-6 Fuses
Part
Number
Location
358337
Lead 55
223316
Lead PF2
223316
Lead PF3
Operation 7