Kohler 14RESL Installation Manual - Page 20

Browse online or download pdf Installation Manual for Portable Generator Kohler 14RESL. Kohler 14RESL 48 pages. Residential and light commercial generator sets
Also for Kohler 14RESL: Troubleshooting Manual (8 pages)

Kohler 14RESL Installation Manual
1.7.1

Fuel Conversion, 14RES/RESL

Two fuel connections on the fuel block allow field-
conversion between natural gas and LP vapor. The fuel
metering valves are factory-set and sealed to comply
with applicable emission standards and to provide the
best possible hot and cold starting.
Note: Do not adjust the factory-sealed fuel-metering
adjustments on the fuel block. Changing the fuel-
metering adjustments may violate federal or state
laws.
Use the following procedure to convert from natural gas
(NG) to LP vapor. The procedure includes moving the
fuel connection from the natural gas to the LP port,
plugging the natural gas port, and disconnecting the
leads for the digital spark advance ignition (DSAI). See
Figure 1-11 or Figure 1-12 for the fuel system
component locations.
Procedure to convert from NG to LP, 14RES/RESL
1. Press the OFF button on the generator set
controller and remove the F3 fuse (located in the
service access area).
2. Disconnect the power to the battery charger.
3. Disconnect the generator set engine starting
battery, negative (--) lead first.
4. Turn off the fuel supply.
5. Remove the hose clamp and fuel hose from the
hose fitting in the fuel block. See Figure 1-13.
6. Remove the hose fitting from the natural gas outlet
port in the fuel block. See Figure 1-13.
7. Remove the plug from the LP port in the fuel block.
See Figure 1-13.
8. Clean the plug with a dry cloth or brush, apply fresh
pipe sealant, and install the plug into the natural
gas outlet port.
9. Clean the hose fitting with a dry cloth or brush,
apply fresh pipe sealant to the threads, and install
the fitting into the LP port.
Note: Do not adjust the fuel metering valves.
10. Slide the hose onto the hose fitting and secure it
with the clamp.
11. Disconnect the DSAI leads for LP. The DSAI leads
are located near the fuel solenoid valve. See
Figure 1-11 or Figure 1-12.
12. Connect and turn on the new fuel supply.
20
Section 1 Installation
1
5
4
1. Fuel block
2. Fuel metering valves—factory-sealed, do not adjust
3. Fuel inlet, 1/2 in. NPT
4. Hose fitting
5. Plug
Figure 1-13 Fuel Block, 14RES/RESL
13. Reconnect the generator set engine starting
battery leads, negative (--) lead last.
14. Reconnect power to the battery charger.
15. Install the F3 fuse and start the generator set by
pressing the RUN button on the generator set
controller.
16. Check for leaks using a gas leak detector.
17. Run the generator set and check the operation.
Use the controller to adjust the output and stability if
necessary. See Section 1.15 for instructions.
18. Press the OFF button to to shut down the generator
set.
Conversion from LP to Natural Gas
To convert from LP vapor to natural gas, follow the fuel
conversion procedure above, moving the hose fitting to
the natural gas port and plugging the LP port. Connect
the DSAI leads for natural gas. See Figure 1-14.
Fuel
Natural Gas
LP
Figure 1-14 DSAI Connection
2
Natural gas
setup shown
3
GM66563
DSAI Leads 65 and N
Connect lead 65 to N
Disconnect
TP-6733 8/11