1.8.6

PIM Input and Output Connections

The optional programmable interface module (PIM)
provides two programmable inputs and six dry contact
outputs, four of which are programmable.
TT-1584
for
PIM
instructions.
Figure 1-13
1
2
3
1. Output connections (3 terminal blocks, 6 outputs)
2. Input connections (2 inputs)
3. Rbus communication connection to generator set terminal
Figure 1-13 Optional PIM
The default settings for the inputs and outputs are
shown in Figure 1-14. To change the input and output
settings, use a personal computer running Kohler
SiteTech
software. See TP-6701, SiteTech Software
Operation Manual, for instructions.
A personal computer running Kohler OnCue
can be used to actively control PIM outputs. See the
®
OnCue
Software Operation Manual for instructions.
Figure 1-14
Connection
PIM Settings
Input 1
None
Input 2
None
Output 1 (Relay 1)
Run
Output 2 (Relay 2)
Common Fault
Output 3 (Relay 3)
Low Battery Voltage
(Programmable)
Output 4 (Relay 4)
Not in Auto (Programmable)
Output 5 (Relay 5)
Cooldown (Programmable)
Output 6 (Relay 6)
Normal Source Failure
(Programmable)
Figure 1-14 PIM Factory Default Inputs and Outputs
18
Section 1 Installation
installation
and
connection
1
1
®
software
1.8.7
Communications Kit Output
Connections
The communications kit includes an interface board,
See
which is factory-installed inside the generator set
enclosure. The inputs and outputs are factory-set to
the settings shown in Figure 1-15.
The outputs are factory-wired from the circuit board to
terminal blocks in the customer connection area. Do
not attempt to connect directly to the interface board.
The output contacts are normally open (NO); outputs
close on activation. Connect customer equipment to
the outputs at the terminal blocks as shown in
Figure 1-15.
Figure 1-15
Connection
Input 1
Input 2
Output 1 (Relay 1)
Output 2 (Relay 2)
Output 3 (Relay 3)
Output 4 (Relay 4)
Output 5 (Relay 5)
Output 6 (Relay 6)
KPS_040
Figure 1-15 Communications Kit Factory Default
Figure 1-16
®
1. Output connections (6 outputs)
Figure 1-16 Communications Kit Output Connections
Communications Kit
Fuel Pressure
Enclosure Intrusion Alarm
Run
Common Fault
Battery Voltage
Fuel Pressure Low Warning
Enclosure Intrusion Alarm Warning
Reserve Oil Empty (oil makeup kit
required)
Inputs and Outputs
commConn
GM85956B
TP-6842 7/15