AB Quality MicroLogix 1100 Installation Instructions Manual - Page 8

Browse online or download pdf Installation Instructions Manual for Controller AB Quality MicroLogix 1100. AB Quality MicroLogix 1100 12 pages. Replacement battery

8
MicroLogix™ 1100 Replacement Battery
Disposal of Damaged and/or Leaking Batteries
ATTENTION
You must wear protective clothing (protective eyewear, clothes, safety shield, and
self-contained breathing apparatus).
Do not:
• pick up ruptured batteries with bare hands. Lithium can cause skin burns. Use tongs,
scoops, or a shovel to place the batteries in a mineral-oil-filled container.
• breathe fumes. Ventilate the area to disperse the fumes before entering the room.
If toxic or corrosive material comes in contact with your eyes or skin, flush with water and
consult a physician. Dispose of clothing that is contaminated.
Use the following procedure to dispose of damaged and/or leaking batteries:
1. Put the damaged batteries in two polyethylene bags and add about 1 ounce of calcium
carbonate (CaCO
salt crystals on the outside of the battery casing.
2. Heat seal both bags.
3. Take the container outside and ventilate the area where you discovered the damaged
batteries.
4. Contact your local EPA office for information about battery disposal companies.

Overheated Batteries

An overheated battery may explode or rupture violently. If you must try to save the battery,
wear the protective clothing described above. If a lithium battery overheats:
• take shelter
• attempt to remove any external source of heat
• remove power from any equipment involved
• remove the battery to a well-ventilated fire-protected area after it cools
Publication 1763-IN003A-EN-P - August 2005
If the batteries are badly damaged and/or leaking, evacuate all personnel
from the immediate area.
) to the inner bag. Slowly-leaking batteries have a deposit of white