Aqua Logic DCS-TI Instruction Manual - Page 3
Browse online or download pdf Instruction Manual for Temperature Controller Aqua Logic DCS-TI. Aqua Logic DCS-TI 5 pages. Dc series single stage digital temperature control
DC SINGLE STAGE TEMPERATURE CONTROL PROGRAMMABLE PARAMETERS TABLE
Parr.
Description
SP1
Set Point
1
2
r0
Differential / Hysteresis
3
r1
Lower value set point
4
r2
Higher value set point
5
d0
Heating or Cooling
6
d2
Time for Defrosting
7
d8
Interval Time between Defrosts
8
c0
Min. time stop for compressor
9
c1
Continuous cycle time
10
c2
On time of fault cycle
11
c3
Off time of fault cycle
12
P0
Temperature scale selection
13
P1
Ambient Probe Adjustment
14
H5
Parameter Access Code
15
H6
Probe input type
16
t0
Max. temperature on display
PARAMETER DESCRIPTIONS
SP = Set Point. Temperature desired to regulate the machine. Can vary
from r1 to r2.
r0 = Differential. Heating: If temperature is ≥ SP then output is OFF. If
temperature is < SP - r0 then output is ON. Cooling: If temperature is ≥
SP + r0 then output is ON. If temperature is < SP then output is OFF.
r1 = Lower Set Point Limit.
r2 = Upper Set Point Limit.
d0 = Heat or Cooling Control. Ht = heating control, Co = cooling control.
d2 = Not used
d8 = Not used.
c0 = Minimum Time for Compressor to be OFF. Minimum time for the
compressor to stop until it can start again.
c1 = Continuous Cycle Time. The remaining time for a continuous cooling
cycle.
c2 = ON Time of fault cycle, during probe error.
c3 = OFF Time of fault cycle, during probe error.
P0 = Selection of Engineering units between F and C.
P1 = Ambient Probe Calibration. Offsets temperature in degrees to
adjust the ambient probe.
H5 = Access Code to Parameters. Factory-set to 0.
H6 = Selection of Input Probe Type: PTC or NTC.
t0 = Temperature Display Limit. Maximum temperature shown on the
display, although the real temperature can be greater.
OPERATION IN CASE OF ERROR
If the probe or thermostat memory should fail, the chiller or heater will turn off.
Error Messages
In normal operation, the probe temperature will be shown. In case of alarm press the "SET" and the "DOWN" ▼ arrow buttons at the
same time to quit the alarm. An error messages will be shown:
•
Er – Memory error
•
-- Shorted –circuited probe error
•
oo- Open probe
Factory
Units
Range
Settings
Degrees
r1 to r6
75
Degrees
1 to 20°
1
-50 to 150 °C
Degrees
30°F
-50 to 302 °F
-50 to 150 °C
Degrees
100°F
-50 to 302 °F
Option
Ht or Co
Co
Minutes
0 to 59
0
Hours
0 to 24
0
Minutes
0 to 59
0
Hours
0 to 24
0
Minutes
0 to 99
0
⁰C / ⁰F
Minutes
0 to 99
0
Option
F
Degrees
-10 to 10°
0
Number
0 to 99
0
Option
Ptc / Ntc
Ptc
-50 to 150 °C
Degrees
100°F
-50 to 302 °F
Page 3 of 5
Note
Change
Aqua Logic, Inc
9558 Camino Ruiz.
San Diego, CA 92126
PH: 858.292.4773 Fax: 858.292.0537
Email: [email protected]
Website: www.aqualogicinc.com
©Aqua Logic, Inc. 2017