Avocent Cyclades PM20-L30A Specification Sheet - Page 2

Browse online or download pdf Specification Sheet for Power distribution unit Avocent Cyclades PM20-L30A. Avocent Cyclades PM20-L30A 2 pages. Cyclades pm series power distribution unit
Also for Avocent Cyclades PM20-L30A: Quick Installation Manual (2 pages), Specification Sheet (2 pages), Brochure (6 pages)

Avocent Cyclades PM20-L30A Specification Sheet
Hardware Specifications – NEMA
Interfaces:
2 RJ-45 RS-232 serial ports (9,600 8-N-1)
10 or 20 NEMA 5-15R outlets
Power*:
PM10-15A
100–125 VAC, 15 A, NEMA 5-15P plug
15 A max. branch circuit rating
15 A max. per NEMA 5-15R outlet
PM10-20A, PM20-20A
100–125 VAC, 20 A, NEMA 5-20P plug
20 A max. branch circuit rating
15 A max. per NEMA 5-15R outlet
PM10-L20A, PM20-L20A
100–125 VAC, 20 A, NEMA L5-20P twist-lock plug
20 A max. branch circuit rating
15 A max. per NEMA 5-15R outlet
PM10-L30A, PM20-L30A
100–125 VAC, 30 A, NEMA L5-30P twist-lock plug
30 A max. branch circuit rating
15 A max. per NEMA 5-15R outlet
Operating
Temperature:
50ºF to 122ºF (10ºC to 50ºC)
Storage
–40ºF to 185ºF (–40ºC to 85ºC)
Temperature:
Humidity:
5% to 95% noncondensing
Dimensions:
(W x D x H)
PM10-15A, -20A, -L20A
17 x 8.25 x 1.75 in. (43.18 x 20.96 x 4.45 cm)
PM10-L30A
17 x 8.5 x 1.75 in. (43.18 x 21.59 x 4.45 cm)
PM20-20A, -L20A, -L30A
1.8 x 2.2 x 66 in. (4.57 x 5.56 x 167.64 cm)
Weight:
PM10
8.8 lb
4.0 kg
PM20
12.4 lb
5.6 kg
Certifications:
FCC Part 15, A
CSA (fully compliant to UL standard)
*Units are certified to 80% of max. current rating.
Part Number
Model
ATP3015-001
PM10-15A
ATP3020-001
PM10-20A
ATP3025-001
PM10-L20A
ATP3036-001
PM10-L30A
ATP2020-001
PM20-20A
ATP2025-001
PM20-L20A
ATP2035-001
PM20-L30A
Description
10 outlets, 15 A max. branch, NEMA 5-15P
10 outlets, 20 A max. branch, NEMA 5-20P
10 outlets, 20 A max. branch, NEMA L5-20P
10 outlets, 30 A max. branch, NEMA L5-30P
20 outlets, 20 A max. branch, NEMA 5-20P
20 outlets, 20 A max. branch, NEMA L5-20P
20 outlets, 30 A max. branch, NEMA L5-30P
Corporate Headquarters
4991 Corporate Drive, Huntsville, AL 35805
TEL 866.277.1924 FAX 256.430.4030
www.avocent.com
Features
Connectivity
RS-232 serial port for configuration and management
Second RS-232 serial port for control-level daisy chaining
(up to 128 outlets)
Full RS-232 signal support allows dial-in access via modem
Administration
Name assignment per IPDU (up to 8 characters)
Name assignment per outlet (up to 16 characters)
Local authentication support (up to 8 users)
Per-outlet access control lists
Management
Independent control of power outlets (power on/off, cycle)
Virtual lock per outlet (on or off states)
Sequential power up with user-defined inter-outlet delays
Global, true RMS current monitoring per IPDU
Two-digit 7-segment LED current display
On/off status LED per outlet
User-defined overcurrent threshold with alarm
Built-in visual and audible alarms
Built-in ambient temperature sensor
Form Factors
Industry's highest outlet density (up to 10 outlets per 1U)
Horizontal (1U) and vertical (0U) models address a wide variety
of applications
Integration Features*
Integrated power management through console and KVM sessions
CLI, menu and GUI interfaces
Multioutlet grouping for devices with redundant power supplies
RADIUS, TACACS+, Kerberos, LDAP, and Active Directory
server-based authentication with local fallback
Token-based strong authentication (RSA SecurID)
Event logging via syslog
Fault notification via e-mail, SMS page, SNMP trap
SNMP integration with enterprise systems
*Features available when product is used in conjunction with Cyclades ACS console servers, DSR
switches, Cyclades OnSite branch office appliance or DSView 3 management software (not included).
NEMA
Inputs
NEMA 5-15P
NEMA 5-20P
on fixed 12 ft power cord
on fixed 12 ft power cord
Outlets
NEMA 5-15R
Avocent, the Avocent logo, The Power of Being There, Cyclades, DSR
and DSView are registered trademarks of Avocent Corporation or its
affiliates. All other marks are the property of their respective owners.
Copyright © 2006. Avocent Corporation. All rights reserved.
1206-PMNEMA-DS
NEMA L5-20P
NEMA L5-30P
on fixed 12 ft power cord
on fixed 8 ft power cord