2VV AirGENIO SUPERIOR Operation Instructions Manual - Page 6

Browse online or download pdf Operation Instructions Manual for Control Systems 2VV AirGENIO SUPERIOR. 2VV AirGENIO SUPERIOR 12 pages.

2VV AirGENIO SUPERIOR Operation Instructions Manual
1. CONTROL

Service menu

Enter code 1616 to access the service menu
Delete/return
Choose this menu
after centring
the screen and
tapping on enter.
MENU - MODE
Setting AUTO or MANUAL may block/unblock certain items
in the service menu.
MENU - HW SETTING
Use this menu to set the detailed behaviour of the inputs
and outputs of the regulators
Door contact (NO/NC)
External control contact
(NO/NC)
Error contact (NO/NC)
Ad 1) – External temperature sensor activation/settings Options:
None – no sensor connected – inactive
EXT-1 (45,46) – sensor connected (must be on terminals 45 y 46)
BMS – sensor active and used from the master system
Ad 2) - Sets the external contact input behaviour. Options:
None – inactive
External control – External switching of device
Night reduction – Night reduction on/off
(settings described below)
Ad 3) - Thermostat (NO/NC)
6
1616
Access menu
Access selected
menu
MANUAL control
Activate/deactivate automatic control of
motor speed according to temperature
Ad 1)
Ad 2)
Ad 3)
2VV.Creating innovative solutions for you and your business since 1995.
MENU - FILTER TIMER
Use this menu to set the period (in motor hours) after which
you will be reminded to replace the filters or reset to timer.
Set the time after which a
notice will appear in the main
screen.
1000h ~ 5000h
Shows the status of the
clogged filter in the main screen
MENU - TEMPERATURE SENSOR
Available only in automatic mode
Use this menu to select the sensor to be used for primary
temperature control
Only available in Manual mode.
Options:
Outlet – Temperature sensor at the outlet (behind the exchanger)
Inlet – Temperature sensor at the inlet (before the exchanger)
Room – Room temperature sensor
Thermostat – Room thermostat (ON/OFF)
Room BMS – Room temperature sensor from master system
Current timer status
RESET button
(use after replacing
filters)