7. MAINTENANCE
7.1 PERIODICAL CLEANING
OF THE VENTILATION UNIT
We suggest regular inspections of the ventilation unit in the in-
terval that must be adjusted depending on current conditions.
In case the unit is not in operation for a longer period of time, we
suggest activation of the unit for 1 hour operation at least every
six months.
ATTENTION
Service of internal components and cleaning of the unit
must be carried out by professional service shop only!
Operation of the unit without the filter is not allowed! Other-
wise the heat exchanger can be damaged!!!
For this maintenance it is always necessary to remove unit from
the working position - there is a risk of injury.
11 mm
Disassembly of the unit only in exceptional cases!!!
Clean the ventilation unit, using a vacuum-cleaner, small brush,
cloth and soapy water especially recuperator. Do not clean the
unit with following: Sharp objects, aggressive chemicals, sol-
vents, abrasive cleaning products, pressured water, pressured air
or steam.
2VV. Creating innovative solutions for you and your business since 1995.
ver.1 06-04-20
7.2 MAINTENANCE
After the time-out limit set for filter check. This means that is ne-
cessary to check and replace the filters.
ATTENTION
In case that filters will not be replaced properly, functionality of the
unit may be reduced the preheater can overheat and ventilator can
be damaged.
After checking or replacing filters, the fouled filter control
must be restarted; see the chapter MENU FILTER TIMER.
13