Environmental
NOTE: Applies to data center environments only.
Air filtration requirements do not apply to IT
equipment designed to be used outside a data
center, in environments such as an office or factory
floor.
Conductive Dust
NOTE: Applies to data center and non-data center
environments.
Corrosive Dust
NOTE: Applies to data center and non-data center
environments.
Airborne Contaminant Level
Class
Gaseous Contamination
Copper Coupon Corrosion Rate
Silver Coupon Corrosion Rate
Air must be free of conductive dust, zinc whiskers, or
other conductive particles.
Air must be free of corrosive dust.
Residual dust present in the air must have a
deliquescent point less than 60% relative
humidity.
G1 as defined by ISA-S71.04-1985.
<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.
9