Dell PowerVault NX3300 Getting Started Manual - Page 9
Browse online or download pdf Getting Started Manual for Storage Dell PowerVault NX3300. Dell PowerVault NX3300 9 pages. Network attached storage system
Also for Dell PowerVault NX3300: Troubleshooting Manual (17 pages), Administrator's Manual (50 pages), Setting Up (2 pages), Setting Up (2 pages), Setting Up (2 pages)
Environmental
NOTE: Applies to data center environments only.
Air filtration requirements do not apply to IT
equipment designed to be used outside a data
center, in environments such as an office or factory
floor.
Conductive Dust
NOTE: Applies to data center and non-data center
environments.
Corrosive Dust
NOTE: Applies to data center and non-data center
environments.
Airborne Contaminant Level
Class
Gaseous Contamination
Copper Coupon Corrosion Rate
Silver Coupon Corrosion Rate
Air must be free of conductive dust, zinc whiskers, or
other conductive particles.
•
Air must be free of corrosive dust.
•
Residual dust present in the air must have a
deliquescent point less than 60% relative
humidity.
G1 as defined by ISA-S71.04-1985.
<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.
9