Miele DA 329 i Operating And Installation Manual - Page 6
Browse online or download pdf Operating And Installation Manual for Ventilation Hood Miele DA 329 i. Miele DA 329 i 40 pages.
– The distance between the top of the
cooker/hob and the bottom of the
cooker hood must measure at least:
– 45 cm above electric cookers/hobs,
– 65 cm above gas cookers/hobs,
– 65 cm above a Miele or Imperial
electric open grill.
For other manufacturer's cooking ap-
pliances maintain the safety distance
as recommended in their Installation
and Operating instructions.
If more than one appliance is fitted be-
neath the cooker hood and they have
different minimum safety distances to
the cooker hood, select the higher dis-
tance.
Safety regulations prohibit the fit-
ting of a cooker hood over solid
fuel stoves.
All ducting, pipework and fittings
must be of non-flammable ma-
terial. These can be obtained from the
Miele Spare Parts department or from
builders' merchants.
The appliance must not be con-
nected to a chimney or vent flue
which is in use. Neither should it be
connected to ducting which ventilates
rooms with fireplaces.
If exhaust air is to be extracted into
a chimney or ventilation duct no
longer used for other purposes, take
professional advice.
6