Miele PUR 68 W Operating And Installation Instructions - Page 29

Browse online or download pdf Operating And Installation Instructions for Ventilation Hood Miele PUR 68 W. Miele PUR 68 W 40 pages. Ventilation system
Also for Miele PUR 68 W: Operating And Installation Instructions (40 pages), Operating And Installation Instructions (40 pages), Operating And Installation Instructions (40 pages), Operating And Installation Instructions (36 pages), Operating And Installation Instructions (40 pages)

Miele PUR 68 W Operating And Installation Instructions
a Extraction
b Recirculation
c Air vent positioned at top for recirculation
de Mounting area (only d is required for recirculation hoods). Wall and ceiling
area for exhaust duct opening and for wall socket installation. Only the wall
socket installation is required for recirculation hoods.
Vent collar  6" (150 mm), with adapter  5" (125 mm).

Distance between cooktop and ventilation hood (S)

Provided a larger distance is not given by the manufacturer of the cooktop, follow
the minimum safety distances between a cooktop and the bottom of the hood.
Please also observe the information contained in the "IMPORTANT SAFETY
INSTRUCTIONS" section.
Cooking appliance
Electric Cooktops
Electric Barbeques and Fryers
Multiburner Gas Cooktops
≤ 43,000 BTU/hr (12.6 kW),
no burner > 15,000 BTU/hr (4.5 kW).
Multiburner Gas Cooktops
≤ 73,800 BTU/hr (21.6 kW),
no burner > 16,500 BTU/hr (4.8 kW)
Multiburner Gas Cooktops
> 73,800 BTU/hr (21.6 kW),
or one of the burners > 16,500 BTU/hr (4.8 kW)
Single Burner Gas Cooktops
≤ 20,500 BTU/hr (6 kW)
Single Burner Gas Cooktops
> 20,500 BTU/hr (6 kW)
≤ 27,600 BTU/hr (8.1 kW)
Single Burner Gas Cooktops
> 27,600 BTU/hr (8.1 kW)
Installation
Minimum distance S
Miele
appliance
24" (610 mm)
26" (660 mm)
26" (660 mm)
30" (760 mm)
30" (760 mm)
Not possible
26" (660 mm)
30" (760 mm)
30" (760 mm)
Not possible
Non-Miele
appliance
29