Eagle Quick Start Guide
Installing the Eagle
1
2
3
4
Prepare the mount
Ø 9/16"
Hang the Eagle
Handle the Eagle carefully
with hands while hanging
it. Use appropriate PPE
Verify that the indicator
cup is in open position
before placing Eagle in
the mount
Connect the Eagle
Swing the recloser from H1
connection ring using a
hotstick to secure the Eagle
in its mount
Ensure that the H1
terminal is securely
latched to the mount
Manually Close the Eagle
Operate the main handle using
a hotstick. The handle will
naturally come back down
after closing the VI
Verify close operation with the
indicator cup
ANSI: Red=Closed, Green=Open
IEC: Red=Open, Green=Closed
Restoration after a Lockout
Fix the Fault
Identify the locked out
recloser with the lockout
LED (flashes once every 4s)
Fix the downstream fault
The Lockout LED may not blink if
the recloser has lost the stored
charge. The indicator cup can be
used to identify the locked out
recloser
1
Reset the Recloser
Operate the main handle
using a hotstick to reset the
recloser.
The Lockout LED will stop
flashing if it was active
2
before resetting
Manually Close the Eagle
Operate the main handle using
a hotstick. The handle will
naturally come back down
after closing the VI
Verify close operation with the
3
indicator cup
PAGE 3 OF 4