Burkert 6519 Operating Instructions Manual - Page 12

Browse online or download pdf Operating Instructions Manual for Industrial Equipment Burkert 6519. Burkert 6519 17 pages. Solenoid valve
Also for Burkert 6519: Manual (4 pages)

Tighten cable plug (for authorized types see data sheet), observing
maximum torque (see "Tab. 1").
Check that seal is fitted correctly.
Connect protective conductor and check electrical continuity
between coil and housing (see "Tab. 2").
NOTE!
If the cable plug EN 175-301-803 is designed in such a way that
the screw is pointing upwards, insert a seal made of a material com-
patible with your process under the screw head.
Note the voltage and current type as specified on the type
label.
Valve type
Cable plug Type
Tightening torque
max. (Nm)
Tab. 1:
Maximum tightening torque of cable plug
12
6516/6517
6518/6519
2506
2508
0.3
1
english
Pesistor
Test voltage
max. 0.1 Ω
Tab. 2:
Test values protective conductor function
6.5 Pneumatic position indicator
Fig. 6:
Pneumatic position indicator
When the valve is switched off, the red indicator pin can be pressed
in without any resistance. When the valve is actuated, the indicator pin
moves out and there is perceptible resistance to pressing it in.
NOTE!
Whenever performing a function test, press in the indicator pin again.
Test current
12 V
1 A
Indicator pin (red)