Chromalox DTS-HAZ Installation Instructions Manual - Page 10
Browse online or download pdf Installation Instructions Manual for Thermostat Chromalox DTS-HAZ. Chromalox DTS-HAZ 12 pages. Microprocessor based temperature control and power connection kit
Optional Wall Mount Kit
The DTS-HAZ may be mounted on vertical surfaces. To
maintain UL/cUL and Class 1, Division 2 compliance,
the user must use the optional Wall Mounting Bracket
Kit (MP-2 DTS-HAZ Mounting Plate Kit, part number
5120-13015).
Considerations:
1. The kit comes complete with two stainless steel
mounting brackets and the necessary hardware to
mount the brackets to the DTS-HAZ.
2. Should the owner use other means to mount the
DTS to a vertical surface, a minimum of 3 inches
or 76 mm must be maintained from the rear of the
DTS-HAZ to the mounting surface. This is neces-
sary to provide adequate airflow across the heat
sink at the rear of the DTS.
.657
[16.69mm]
.875
[22.23mm]
Ø.218 [Ø5.54mm]
Ø.390 [Ø9.91mm]
.875
[22.23mm]
3.000
[76.20mm]
10
3. When installing the DTS on a vertical surface, the
Pipe Standoff is not used and is typically replaced
by rigid 1" NPT conduit. The conduit shall terminate
into the Compression Fitting.
Ordering Information:
Wall Mount Kit PCN (Part Number): 318043
RECOMMENDED - WALL MOUNT LAYOUT
MAXIMUM #10 STUD
7.750 [196.85mm]
4.500
16 ga Stainless Steel
[114.30mm]
Bracket Material:
0.059 " (1.5mm) nominal