Technician Settings (Cont.)
P06 – Enable/Disable Temperature sensor /
Aquastat logic
1. Press the [SELECT] and [+] buttons
simultaneously.
2. "P06" and the number "0" or "1" will appear
on display.
3. Use the [+] and [-] buttons to select between:
"0" Logic set by both TEMPERATURE
SENSOR
and AQUASTAT (default).
"1" Logic set by TEMPERATURE sensor only.
"2" Logic set by AQUASTAT sensor only
Logic by temperature
sensor & aquastat
P07 – Not in use
1. Press the [SELECT] and [+] buttons simultaneously.
2. "P07" will appear on display.
3. Proceed to P08.
P08 - MODBUS MAC Address
(for MDB models only)
1. Press the [SELECT] and [+] buttons
simultaneously.
2. "P08" and the MODBUS MAC Address will
appear on display.
3. Use the [+] and [-] buttons to set the MAC
Address of the unit.
4. Setting the MAC address for the unit
will make it available through the home
automation system.
Range: 0 – 60. Select "0" for
NO COMMUNICATION system (default).
Logic by temperature
Logic by temperature
sensor & aquastat
sensor only
Logic by temperature
Logic by aquastat
sensor only
sensor only
MODBUS
MAC Address
16
P09 – Test conditions mode /
Technician commissioning mode
Turn ON test conditions to check the functionality
of the system regardless of temperature sensors
parameters (i.e. during the summer).
In test conditions, the Ambient temperature is
always -7°C/19°F.
Logic by aquastat
sensor only
1. Press the [SELECT] and [+] buttons
simultaneously.
2. "P09" will appear on display. The hours will blink.
3. Use the [+] button to enter
test/commissioning mode – the word "Test"
will appear on display.
4. Use the [-] button to manually exit test/com-
missioning mode – the word "Test" will disap-
pear from display.
Note: If the technician did not manually exit test/
commissioning mode, the unit will automatically
return to normal mode after 5 hours.
P11 – Master/Slave
1. Press the [SELECT] and [+] buttons
simultaneously.
2. "P11" will appear on display.
3. Use the [+] and [-] buttons to select between:
• "ΠA" - Master (When using one FPC-02-OD
or when controlling other
• "SL" - Slave (controlled by another
FPC-02-OD connected to A,B)
Test
conditions mode
Master
Slave
17