ELECTRICAL INSTALLATION:
1. Connect power supply wires appropriately sized and protected by double pole circuit breakers to the
input terminals on the heater (hard wired) as shown in the Figure 2 wiring diagrams below. Refer to
Table 1 above on Page 1 for the voltage, amp and phase ratings of the supply power. Use 2 X 2 wire plus
ground supply wires for the 2 module heaters, and 3 X 2 wire plus ground for the 3 module heaters.
2. Ensure each pair of wires are connected to the respective relay terminals. Connect 1 pair at a time.
3. Ensure water inlet/outlet valves are both open.
4. Turn on circuit breakers. Carefully ensure the red LED is illuminated at each circuit board module. The
unit is almost ready for use. Shut off circuit breakers.
5. Install cover. Install the (4) cover mounting screws. Turn on circuit breakers. Unit is now ready for use.
6. Local plumbing and electrical codes must be followed in this installation of water heater and the
accessories. Failure to comply with code requirements voids warranty.
7. Temperature adjustment potentiometer is standard equipment on (L) Low Activation and (S) Standard
Activation models.
2 Module Units / 60-80 amps
A=L1 (Black) B=L2 (Red)
Figure 2 - Wiring Connections
3 Module Units / 90-120 amps
A=L1 (Black) B=L2 (Red)