AquaStar PLP300S-SVRS Installation, Operation And Service Manual - Page 2

Browse online or download pdf Installation, Operation And Service Manual for Water Pump AquaStar PLP300S-SVRS. AquaStar PLP300S-SVRS 2 pages. Approved smart pipeline pumps

Installation Operation and Service Manual
WIRING TO PUMP (COMMUNICATION MODULE TO
PUMP)
1. Route the "TO PUMP" black cable out of the load center
and to the PipeLine Smart Pump. If the included cable
length is too long, wrap the excess cable and zip tie inside
the load center.
2. It is recommended to zip tie the cable alongside electrical
conduit or PVC plumbing to prevent tripping hazards.
3. Insert the cable connector end into the "Communication
Port" on the side of the PipeLine Smart Pump and turn
the locking ring clockwise to lock. See Figure 2 for the
location.
4. More than one pump can be controlled by a PLCM. To
connect more than one pump to a PLCM, connect all "TO
PUMP" cables together outside of PLCM housing. Ensuring
all red and black wires are matched to their corresponding
counterparts. See Figure 3 for wiring example.
PUMP SETUP
Once the wiring is complete, switch power ON to the
pump and load center by reconnecting power at the
circuit breaker.
Press the "Menu" button to enter the settings menu.
Use buttons "Up" and "Down" to highlight the "RS485" option and press "Enter. "
The baud rate is set to 9600 bps. Do not modify this setting.
Use buttons "UP" and "Down" to highlight the "Replica Address" (formerly called "Slave Address") and press "Enter"
to modify.
The Replica Address (formerly called Slave Address) is a unique pump ID to be used on external automation
systems when multiple pumps are being controlled. This is set to "1" by default.
If multiple pumps are being controlled on the same system, ensure that each pump has its own unique Replica
Address (formerly called Slave Address).
Press "Enter" to edit and then use buttons "Up, " "Down, " "Left, " and "Right" to adjust these settings and press
"Enter" to save.
Press "ESC" button to return to the previous screen or repeatedly press to return to the home screen.
CONTROLLER SETUP
1. Go into the Controller's Settings for variable speed pumps.
a. Refer to the controller's user manual for help.
2. Select the pump, with the correct pump Replica Address (Formerly called Slave Address) in the correct slot for your
controller, and identify your Pipeline Pump as a Pentair Intellifl ow VS Pump.
3. Select the RPM Range of the Pump and Change the Maximum RPM to 3400 and the Minimum RPM to 800
4. Set the prime setting within the controller to 2900 RPM for 2 minutes by default. This can be adjusted if needed.
5. Repeat Steps 2-4 for each pump connected to the PLCM.
6. Run a test to ensure the you have identifi ed the correct pumps for your desired functions.
FIGURE 2
Pump Union & Nut
Communication Port
Wiring Compartment
FIGURE 3
WIRE NUT
TO PUMP 1
TO PUMP CABLE
TO PUMP 2
WIRE NUT
Continued
Strainer Lid & Locking Rings
Drive Display Cover
Motor Drive
Motor Fan Cover
Vibration Dampening
Motor Support
TO CONTROLLER
Rev: