Aquatel D110-S Instruction Manual - Page 8
Browse online or download pdf Instruction Manual for Monitor Aquatel D110-S. Aquatel D110-S 12 pages. Wireless level monitor
system setup
10
Programming of the D110 system is done via the Display Unit "System Setup"
menu. To enter the "System Setup", hold the menu button down for 3 seconds
until you see the "System Setup" screen.
Note:
changes made in display unit are not instantly transmitted to the tank unit. the tank unit
will only update at the next scheduled reading interval. to force an update remove the tank unit
lid and press the reset button.
display
Here you can change the language to either English to French, adjust the clock to be
either 12 or 24hr, adjust how long you want the display to stay on after any button is
pushed and select the temperature either Fahrenheit or Celsius.
tank unit setup
11
T o add a new Tank Unit simply select the
"Add a new tank" by pressing the menu
button when highlighted. You will be asked
to push the reset button of the Tank Unit,
this allows the Display to see the Tank Units
system ID and you will then be prompted
to select a name for the Tank Unit you are
pairing with the Display Unit.
A s you continue to setup the Tank Unit you will be asked to set the High and Low
level alarm points, tank depth as measured in
further information on how to set up the top air gap, see
the Tank Unit to be in Test Mode or not. Test Mode is helpful when setting up the
system to check the communication range between the Display and Tank Units.
Please ensure that you take out of Test Mode once you have checked the range. If
left in Test Mode, the batteries in the Tank Unit will run flat after 4-5 days.
Set clock and change how long the display stays on
Add, delete & rename Tank Units, Adjust alarm levels etc
Adjust Tank Unit update interval, turn reading beeps on/
off etc
, the top air gap distance (for
3
– 7 –
and whether you wish
7