● EAIRC-MS Types
HP
Air Curtain
Air flow type
Air volume (high)
Air volume (medium)
Air volume (low)
Air flow length (A)
Heating capacity (nominal)
Cooling capacity (nominal)
Heating capacity with air in 20 °C, air
out 40 °C
Heating capacity with air in 20 °C, air
out 35 °C
Heating capacity with air in 20 °C, air
out 30 °C
Max inst. height in good conditions
Max inst. height in normal conditions m
Max inst. height in bad conditions
Refrigerant
Hot gas temperature
Pressure
Tubing Gas
Tubing Liquid
Fan
Fan type
Operating current (high)
Electrical consumption (high)
Operating current (med)
Electrical consumption (med)
Operating current (low)
Electrical consumption (low)
Protecting fuse
Noise
Dimensions (L/H/D):
Weight
Mini ECOi with air out 40 °C
Mini ECOi with air out 35 °C
Mini ECOi with air out 30 °C
ECOi with air out 40 °C
ECOi with air out 30 °C or 35 °C
GHP all temperatures
All combinations under rated conditions. Heating: Outdoor +7 °C DB/+6 °C WB, Indoor +20 °C DB. In case of lower outdoor
temperatures a higher capacity outdoor unit model may be necessary
*1 Rated Conditions Cooling: Outdoor +35 °C DB, Indoor +27 °C DB/+19 °C WB, Discharge temp. ≥ 16 °C.
*2 Or bigger size.
PAW-10EAIRC-MS
m³/h
m³/h
m³/h
m
kW
kW
*1
kW
kW
kW
m
m
°C
bar
mm
mm
A
kW
A
kW
A
kW
A
dB(A)
mm
kg
U-4LE1E5/8
*2
U-4LE1E5/8
*2
U-4LE1E5/8
*2
All models
All models
All models
4
Standard
1800
1500
1200
1.0
11.4
9.2
11.9
8.9
5.9
3.0
2.7
2.4
R410a
70
45
15.88
9.52
230V/50Hz/1/N/PE
EC
2.10
0.44
0.80
0.17
0.30
0.06
M16A
40–55
1210 x 260 x 490
60
U-6LE1E5/8
U-4LE1E5/8
U-4LE1E5/8
All models
All models
All models
26
10
PAW-20EAIRC-MS
2210 x 260 x 490
*2
*2
*2
2700
2300
1900
2.0
31.5
17.5
17.9
13.4
8.9
3.0
2.7
2.4
70
45
22.22
9.52
EC
4.20
0.89
1.60
0.34
0.60
0.12
M16A
40–57
128