BIOMICROBICS BioBarrier 0.5-N Installation Manual - Page 4

Browse online or download pdf Installation Manual for Water System BIOMICROBICS BioBarrier 0.5-N. BIOMICROBICS BioBarrier 0.5-N 13 pages. For use with nsf/ansi std. 40 class i/std. 350 class r, ansi/nsf std. 245
Also for BIOMICROBICS BioBarrier 0.5-N: Owner's Manual (7 pages)

®
SaniTEE
Installation Screen
1. Check the specifications of the BioBarrier unit to determine the required number
of SaniTEE screens to be installed.
2. A 4" SaniTEE
®
JUST PRIOR to the BioBarrier system. The center of the SaniTEE
be at least 38 inches [96.5 cm] off the bottom of the tank.
3. Place the SaniTEE
should fit snugly into the outlet tee.
4. OPTIONAL -
EXTENDING SWAB HANDLES
may be easily extended using ¾" schd 80 pipe and matching couplings. Cut ¾"
pipes to the desired length, glue and connect each extension pipe to the existing
pipes using slip-to-slip couplings. When completed, glue the supplied swab
handle to each pipe end.
5. Reattach the SaniTEE
or added extension pipe.
BioBarrier MODULE INSTALLATION
Use safe lifting techniques to set module in tank. Be sure all lifting equipment is clear of obstructions such as power lines
and trees.
1.
The BioBarrier system should be placed as far toward the outlet end of the treatment tank as possible.
2. Before installation may begin, check the tank to ensure it is level within ¼" [6 mm] from inlet to outlet and ¼"
[6 mm] from side to side to side.
3. Install the SaniTEE® wastewater screen in the outlet tee of the settling tank/compartment (see SaniTEE®
Installation instructions).
4. If a pump tank is used after the BioBarrier system, then this tank must be placed as close to the BioBarrier
tank as possible.
5.
If the tank is smaller than the minimum dimensional range specified, the BioBarrier® system may not
operate properly. The effluent quality could suffer and may not meet site requirements.
fits in the 4" septic tank outlet tee or sweep (Schd 35, 40 & 80)
into the outlet tee. DO NOT USE GLUE. The SaniTEE
®
handle with solvent welding to the ¾" Schd 80 swab shaft
®
outlet MUST
®
– The exterior cleaning swab pipes