Dictator RZ-24-05 Central Technical Manual - Page 7

Browse online or download pdf Technical Manual for Door Opening System Dictator RZ-24-05 Central. Dictator RZ-24-05 Central 13 pages.
Also for Dictator RZ-24-05 Central: Technical Manual (12 pages)

Dictator RZ-24-05 Central Technical Manual
Technical manual: Central unit RZ-24-05
4.2 TECHNICAL DATA OF THE RZ-24-05
Supply voltage
Power consumption
Secondary output voltage
Secondary total load
Operating temperature
Max. number of detectors 20
Power consumption of
detection loop
LED indicators
IP rating
IMPORTANT
In total the RZ-24-05 central provides 0.5 A for the supply of the con-
nected fire detectors, magnets etc.
In case the maximum power consumption is exceeded, the RZ-24-05
will automatically switch off. This also happens when it is overheated!
DICTATOR Technik GmbH · +49 (0)821 246730 · [email protected] · en.dictator.de · 20.05.13
85 VAC - 264 VAC
about 14 W, own consumption about 40 mA
24 VDC ±10 %
0.5 A (supply of fire detectors, electromagnets and other consumers)
0 °C to +40 °C
Alarm: I > 12 mA
Interruption: I < 3 mA
Short circuit current: max. 45 mA
Quiescent current: 4.5 mA
Line tension: Ulin = 20.5...21.4
Green LED is on: detection loop is ready.
Red LED is on: detection loop is triggered.
Yellow LED is on/flashes: there is a disturbance.
IP 30
7