Epever LS2024B User Manual - Page 2

Browse online or download pdf User Manual for Controller Epever LS2024B. Epever LS2024B 2 pages. Landstar b series; ls-b series solar charge controller
Also for Epever LS2024B: Quick Start Manual (2 pages)

Epever LS2024B User Manual
battery type (factory default value is the same as sealed type):
A. Over Voltage Disconnect Voltage > Charging Limit Voltage ≥ Equalize Charging
Voltage ≥ Boost Charging Voltage ≥ Float Charging Voltage > Boost Reconnect Charging
Voltage.
B. Over Voltage Disconnect Voltage > Over Voltage Reconnect Voltage.
C. Low Voltage Reconnect Voltage > Low Voltage Disconnect Voltage ≥ Discharging Limit
Voltage.
D. Under Voltage Warning Reconnect Voltage > Under Voltage Warning Voltage ≥
Discharging Limit Voltage.
E. Boost Reconnect Charging voltage > Low Voltage Disconnect Voltage.
CAUTION: Please refer to user guide or contact with the sales for the
detail of setting operation.
(2)Load Set Mode
1)Manual Control(default ON)
The load is turned ON/OFF via the button.
2)Light ON/OFF
3) Light ON/OFF + Timer
4)Time Control
Control the load on/off time through setting real-time clock.
6 Protections
 PV Over Current
When the charging power of the PV array exceeds its rated power, it will be charged at
the rated power.
PV Short Circuit
When not in PV charging state, the controller will not be damaged in case of a
short-circuiting in the PV array.
PV Reverse Polarity
When the polarity of the PV array is reversed, the controller may not be damaged and
can continue to operate normally after the polarity is corrected.
Battery Reverse Polarity
Fully protected against battery reverse polarity; no damage to the controller will result.
Correct the miswire to resume normal operation.
 Battery Over Voltage
When the battery voltage reaches the over voltage disconnect voltage, it will
automatically stop battery charging to prevent battery damage caused by over-charging.
Battery Over Discharge
When the battery voltage reaches the low voltage disconnect voltage, it will
automatically stop battery discharging to prevent battery damage caused by
over-discharging. (Any controller connected loads will be disconnected. Loads directly
connected to the battery will not be affected and may continue to discharge the battery.)
Battery Overheating
The controller can detect the battery temperature through an external temperature
sensor. The controller stops working when its temperature exceeds 65 ° C and begins
working when its temperature is below 55 ° C.
Load Overload
When the load is overloading (The overload current is ≥ 1.05 times the rated load
current), the controller will automatically cut off the output. If the load reconnects
automatically five times (delay of 5s, 10s, 15s, 20s, 25s), it needs to be cleared by
pressing the Load button restarting the controller, switching from Night to Day
(nighttime > 3 hours).
Load Short Circuit
When the load is short circuited (The short circuit current is ≥ 2 times the rated controller
load current), the controller will automatically cut off the output. If the load reconnects
the output automatically five times (delay of 5s, 10s, 15s, 20s, 25s), it needs to be
cleared by pressing the Load button, restarting the controller or switching from Night to
the Day (nighttime > 3 hours).
BEIJING EPSOLAR TECHNOLOGY CO., LTD.
3
Tel:+86-10-82894112 / 82894962
Controller Overheating
The controller is able to detect the temperature inside the battery through an optional
remote sensor. The controller stops working when its temperature exceeds 85 ° C and
begins to working when its temperature is below 75 ° C.
TVS High Voltage Transients
The internal circuitry of the controller is designed with Transient Voltage Suppressors
(TVS) which can only protect against high-voltage surge pulses with less energy. If the
controller is to be used in an area with frequent lightning strikes, it is recommended to
install an external surge arrester.
7 Troubleshooting
Faults
Possible reasons
Charging LED
indicator off during
daytime when
PV array
sunshine falls on
disconnection
PV modules
properly
Wire connection is
correct, the
Battery voltage is
controller is not
lower than 8V
working.
Battery indicator
Battery over
green slowly
voltage
flashing
Battery indicator
Battery over
red on solid
discharged
Battery indicator
Battery
red slowly flashing
Overheating
Charge, Load and
Controller
Battery(orange)indi
Overheating
cator flashing
Load indicator red
Load Overload
slowly flashing
Load indicator red
Load Short Circuit
fast flashing
8.Technical Specifications
Item
LS1024B
System nominal voltage
Battery Types
Rated charge current
Rated discharge current
Working Voltage range of
controller
Max. PV open circuit
voltage
Self-consumption
Charge circuit voltage
drop
Discharge circuit voltage
drop
Temperature compensate
coefficient
Working environment
temperature
Relative humidity
Enclosure
Grounding
138.6x69.3
Dimension
x37mm
Mounting dimension
126mm
Mounting hole size
Terminal
Weight
0.13kg
9.Disclaimer
This warranty does not apply under the following conditions:
 Damage from improper use or use in an unsuitable environment.
 PV or load current, voltage or power exceeding the rated value of controller.
 The controller is working temperature exceed the limit working environment
temperature.
 User disassembly or attempted repair the controller without permission.
 The controller is damaged due to natural elements such as lighting.
 The controller is damaged during transportation and shipment.
Any changes without prior notice! Version number:V2.5
Website:www.epsolarpv.com/www.epever.com
Troubleshooting
Confirm that PV and battery wire
connections are correct and tight
Please check the voltage of battery. At
least 8V voltage to activate the
controller.
Check if battery voltage is higher than
OVD(over voltage disconnect voltage),
and disconnect the PV.
When the battery voltage is restored to
or above LVR(low voltage reconnect
voltage), the load will recover
The controller will automatically turn the
system off. But while the temperature
decline to be below 55 º C, the controller
will resume.
When heat sink of controller exceeds
85℃, the controller will automatically cut
input and output circuit. When the
temperature below 75℃,the controller
will resume to work.
①Please reduce the number of electric
equipments.
②Restart the controller.
③wait for one night-day cycle (night
time>3 hours).
①Check carefully loads connection, clear
the fault.
②Restart the controller.
③wait for one night-day cycle (night
time>3 hours).
LS2024B
12/24VDC Auto
Sealed/Gel/Flooded/User
10A
20A
10A
20A
8~32V
50V
≤8.4mA/12V;≤7.8mA/24V
≤0.28V
≤0.20V
-3mV/℃/2V (default)
-35℃~+50℃
≤95% (N.C.)
IP30
Common Positive
159.6x81.4
x47.8mm
147x50mm
Φ4.3
Φ4.3
2
2
4mm
10mm
0.3kg
4
LS3024B
30A
30A
200.6x101.3
x57mm
190x70mm
Φ4.5
2
10mm
0.5kg