Dieffematic EKOS M1 230 Instructions

Browse online or download pdf Instructions for Control Unit Dieffematic EKOS M1 230. Dieffematic EKOS M1 230 2 pages.

Dieffematic EKOS M1 230 Instructions
L2
P1
T1
T2
L1
L3
1234
J1
SELECTION
P2
OPTIONS 1-8
5678
P2
L4 L5
L6 L7 L8
1
2 3 4
5 6 7 8 9 10 11 12
N.C.
N.C.
N.C.
COM
N.C.
N.O.
N.O.
N.C.
COM
Terminals Type
Description
1 - 2com
NO
START contact (Alternate Pulse OPEN/STOP/CLOSE/STOP)
3 - 2com
NO
PEDESTRIAN contact
4 - 6com
NC
BAND/PHOTOCELL OPENING contact (If you do not use it, please close the contact)
5 - 6com
NC
PHOTOCELL CLOSING contact (If you do not use it, please close the contact)
7 - 6com
NC
STOP contact (If you do not use it, please close the contact)
9 - 8com
NC
LIMIT SWITCH OPENING contact
10 - 8com
NC
LIMIT SWITCH CLOSING contact
11 - 12
24V ~
Photocells + accessories 24VAC 250mA power
13-14-15
220V ~
MOTOR input (13-14 electrical phases with a capacitor in parallel) (15 neutral/common)
16 - 18
220V ~
FLASHING LIGHT input
17 - 18
220V ~
COURTESY LIGHT input
19 - 20
220V ~
LINE input 220VAC
21 - 22
ANTENNA input (21 joiner / 22 signal)
13 14 15 16 17 18 19 20
COM
EKOS M1 230
INSTRUCTIONS:
TECHNICAL SPECIFICATIONS
Voltage
Power
Accessory power output
Automatic closing time
Operating time
Slowing time
Courtesy light time
Number of codes
Transmitters
Frequency
Operating temperature
Sensibility
Homologation
JUMPER J1
Radio memory opening by transmitter.(Possibility of storing from the ou-
tside the transmitters without operating on the control panel).
ON
Insert jumper:
TRIMMER T1
The Power Trimmer regulates the pair and the sensitivity in normal operation.
TRIMMER T2
The Power Slow Trimmer regulates the pair and the sensitivity in slowing.
-
+
The pair increases turning the trimmer in clockwise.
BUTTON P1
RADIO PROG button for the storage of the transmitters
BUTTON P2
TIME PROG button for the storage of the operating time
LED READING
L1
STATUS Led
L2
RADIO Led
L3
PROGRAMMING TIME
Led
L4
START Led
L5
PEDESTRIAN Led
L6
PHOTOCELL Led
L7
L. S. OPENING Led
L8
L. S. CLOSING Led
L7+L8 STOP Led
v M 01022012
220 VAC +/- 10%
550 W
24 VAC 250mA
5 to 120 sec
3 to 120 sec
2 to 120 sec
2 to 180 sec
254 codes
Fix\Rolling code
433.92 / 868 Mhz
0 to 70°C
–100dBm
Conf ETS 300-220/ETS 300
-683
OFF
On when the control panel is powered
On when you log in the radio memory
The led flashes during the programming
On when you give a pulse
On when you give a pedestrian pulse
On when the potocells are aligned
On when the limit switch is in N.C.
On when the limit switch is in N.C.
Both on when the stop is in N.C.