Archive MT6070iH Installation Instruction - Page 2
Browse online or download pdf Installation Instruction for Storage Archive MT6070iH. Archive MT6070iH 2 pages.
EasyBuilder 8000 Software Settings
6
Launch EasyBuilder 8000 software, select your
project file, press F7 shortcut key to open
the download dialog box:
Select Ethernet > IP tab > Enter your HMI IP
> Click Download to download this project
file to HMI.
( Please refer to EasyBuilder 8000 User Manual
for software operation details )
Communication Connections
7
PIN#
COM1 / COM2 [RS232]
1
2
3
4
5
6
7
8
9
COM1 / COM3 [RS485]
PIN#
COM3 [RS232]
1
2
3
4
5
6
7
8
9
DIP SW Settings
8
SW1
ON
OFF
OFF
OFF
OFF
NOTE:
1. COM1 [RS232] RTS/CTS & COM3 [RS232] can't be used
simultaneously.
2. COM1 [RS485] / COM3 [RS485] with isolation protection.
Symbol
COM1 [RS232]
COM2 [RS232]
Not used
RxD
Received Data
TxD
Transmitted Data
TxD
Transmitted Data
GND
Signal Ground
RxD
Received Data
RTS
Ready to send output
CTS
Clear to send input
Not used
Com1
Com1
Com3
Symbol
[RS485]2w
[RS485]4w
[RS485]
Rx-
Data-
Rx-
Rx+
Data+
Rx+
Tx-
Tx-
Tx+
Tx+
GND
Signal Ground
Data-
Data-
TxD
RXD
Data+
Data+
SW2
SW3
SW4
Mode
OFF
OFF
ON
Touch Screen Calibration Mode
ON
OFF
ON
Hide HMI System Setting Bar
OFF
ON
ON
Boot Loader Mode
OFF
OFF
ON
Normal
OFF
OFF
OFF
Not supported
NOTE:
CAUTION
installing the unit. Contact your local authorities to determine which codes apply.
The MT6000/8000i can be powered by DC power only, voltage range: 24±20% Volts DC,
Power
compatible with most controller DC systems. The power conditioning circuitry inside the unit is
accomplished by a switching power supply. The peak starting current can be as high as 2A.
If the display does not come on within 5 seconds of power up, remove power. An internal fuse
Fusing
will prevent damage if the polarity of the DC power is incorrect. Check wiring for proper
Require-
connections and try to power up again.
ments
An Internal fuse will prevent damage for over voltage condition however it isn't guaranteed. DC
High
voltage sources should provide proper isolation from main AC power and similar hazards.
Voltage
A Hard-wired EMERGENCY STOP should be fitted in any system using an MT6000/8000i to
Emergency
comply with ICS Safety Recommendations.
Stop
Do not power the MT6000/8000i and inductive DC loads, or input circuitry to the controller, with
Supply
the same power supply. Note: The 24 VDC output from some controllers may not have enough
Voltage
current to power the MT6000/8000i.
Condition
a. Wire lengths should be minimized (Max: 500m shielded, 300m unshielded).
Wire
b. Wires should be run in pairs with a neutral or common paired with a hot or signal line.
Routing
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices.
d. Keep AC, high energy, and rapidly switching DC wiring separate from signal wires.
e. Equip ungrounded DC supplies with a resistor and capacitor in parallel to earth ground.
This provides a path for static and high frequency dissipation. Typical values to use are 1MOhm
and 4700pF.
DANGER
Hardware
The system designer should be aware that devices in Controller systems could fail and thereby
Considerations
create an unsafe condition. Furthermore, electrical interference in an operator interface can lead
to equipment start-up, which could result in property damage and/or physical injury to the
Com3
operator.
[RS232]
If you use any programmable control systems that require an operator, be aware that this
potential safety hazard exists and take appropriate precautions. Although the specific design
steps depend on your particular application, the following precautions generally apply to
installation of solid-state programmable control devices, and conform to the guidelines for
installation of Controllers recommended in NEMA ICS 3-304 Control Standards.
To conform with ICS Safety Recommendations, checks should be placed in the controller to
Programming
ensure that all writable registers that control critical parts of plant or machinery have limit
Considerations
checks built into the program, with an out-of-limit safe shut down procedure to ensure safety of
personnel.
Transmit
Receive
Limited Warranty
This product is limited warranted against defects in design and manufacture. The proven
defective product will either be repaired or replaced, at Weintek's discretion. This warranty
shall not cover any product which is
(a) Out of warranty period which is 1 year from the date of purchase.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.
Make sure that all local and national electrical standards are met when
GME680700_MT6/8070iH2/iH3_MT6/8100iV2_Installation_120509