Siemens SIMATIC ET 200AL Manual - Page 18

Browse online or download pdf Manual for Industrial Equipment Siemens SIMATIC ET 200AL. Siemens SIMATIC ET 200AL 38 pages. 10-link digital output module dq 8x24vdc/2a 8xm12
Also for Siemens SIMATIC ET 200AL: Manual (50 pages), Manual (38 pages), Manual (32 pages), Manual (37 pages), Equipment Manual (46 pages), Manual (26 pages), Equipment Manual (28 pages), Equipment Manual (27 pages), Manual (25 pages)

Siemens SIMATIC ET 200AL Manual
Wiring
3.2 Pin assignment
Pin assignment of the socket for loop-through of the supply voltage
The table below shows the pin assignment of the socket for loop-through of the supply
voltage.
Table 3- 4
Pin
1
2
3
4
NOTICE
ET-Connection/supply voltage
Observe the correct wiring of the M8 sockets for ET-Connection and the supply voltage.
Mixing up the connector for ET-Connection and the connector for the supply voltage can
destroy the module.
18
Pin assignment of the supply voltage socket
Assignment
X81 socket (POWER output)
Supply voltage 1L+ (non-switched)
Ground 2M (switched)
Ground 1M (non-switched)
Load voltage 2L+ (switched)
Assignment of the wire color
of the power line cable
Brown
White
Blue
Black
Communication module CM 4xIO-Link 4xM12(6ES7147-5JD00-0BA0)
Front view of the
socket
Manual, 10/2017, A5E32352322-AE