Also for Siemens simatic ET 200MP: Manual (40 pages), Manual (29 pages), Manual (47 pages), Manual (26 pages), Manual (28 pages), Manual (50 pages), Manual (34 pages), User Manual (44 pages), Manual (30 pages), Manual (25 pages), Manual (42 pages), Manual (28 pages), Manual (33 pages), Manual (49 pages), Manual (36 pages), Manual (39 pages), Manual (28 pages), Equipment Manual (35 pages), Equipment Manual (32 pages), Manual (29 pages), Manual (34 pages), Manual (36 pages), Equipment Manual (50 pages), Manual (45 pages)

Siemens simatic ET 200MP Manual
Meaning of the LED displays
The following table explains the meaning of the status and error displays.
RUN and ERROR LED
Table 5- 1
Status and error displays RUN and ERROR
LED
RUN
ERROR
Off
Off
Off
Flashes
On
Off
Flashes
Flashes
CHx LED
Table 5- 2
CHx status display
LED CHx
Off
On
DI 16x230VAC BA Digital Input Module (6ES7521-1FH00-0AA0)
Manual, 09/2016, A5E03485975-AD
Meaning
Voltage missing or too low at backplane bus
Module starts up
Module is ready
Hardware defective
Meaning
0 = Status of the input signal
1 = Status of the input signal
5.1 Status and error displays
Remedy
Switch on the CPU and/or the system pow-
er supply modules.
Verify that the U connectors are inserted.
Check to see if too many modules are in-
serted.
---
Replace the module.
Remedy
---
---
Diagnostic alarms