Also for Siemens simatic ET 200MP: Manual (40 pages), Manual (24 pages), Manual (29 pages), Manual (47 pages), Manual (26 pages), Manual (28 pages), Manual (50 pages), Manual (34 pages), User Manual (44 pages), Manual (30 pages), Manual (25 pages), Manual (42 pages), Manual (28 pages), Manual (33 pages), Manual (49 pages), Manual (36 pages), Manual (39 pages), Manual (28 pages), Equipment Manual (35 pages), Equipment Manual (32 pages), Manual (29 pages), Manual (34 pages), Manual (36 pages), Manual (45 pages)

Siemens simatic ET 200MP Equipment Manual
Property
Supply voltage
PROFINET IO
PROFINET interface (X1 P1R
and X1 P2R)
Operation of the CPU as
IO controller
I-device
Accessories
You can find information on "Accessories/spare parts" in the S7-1500, ET 200MP system
manual (http://support.automation.siemens.com/WW/view/en/59191792).
3.4

Firmware functions

Functions
The CPU 1513‑1 PN supports the following firmware functions:
Function
Integrated system
diagnostics
Integrated Web server
CPU 1513-1 PN (6ES7513-1AM03-0AB0)
Equipment Manual, 11/2022, A5E40881673-AC
Description
The 24 V DC supply voltage is fed in via a 4-pin plug loc­
ated at the bottom of the CPU.
The interface has two ports. In addition to basic
PROFINET functionality, its also supports PROFINET IO RT
(real time) and IRT (isochronous real time).
IO controller:
As an IO controller the CPU addresses the connected
IO devices
I-device:
As an I-device (intelligent IO device) the CPU is
assigned to a higher-level IO controller and is used in
the process as an intelligent pre-processing unit of
sub-processes
Description
The system automatically generates the messages for the
system diagnostics and outputs these messages via a
programming device/PC, HMI device, the Web server or
the integrated display. System diagnostics information is
also available when the CPU is in STOP mode.
The Web server lets you access the CPU data by means of
a network. Evaluations, diagnostics, and modifications
are thus possible over long distances. Monitoring and
evaluation is possible without STEP 7; all you need is a
Web browser. Make sure that you take appropriate meas­
ures (e.g. limiting network access, using firewalls) to pro­
tect the CPU from being compromised.
Product overview
3.4 Firmware functions
Additional information
Chapter Connecting up (Page 30)
S7‑1500, ET 200MP system manu­
al
(http://support.automation.
siemens.
com/WW/view/en/59191792)
PROFINET function manual
(https://support.industry.siemens.
com/cs/ww/en/view/49948856)
Additional information
Diagnostics function manual
(https://support.industry.siemens.
com/cs/ww/en/view/59192926)
Web server function manual
(https://support.industry.siemens.
com/cs/ww/en/view/59193560)
Security with SIMATIC S7 control­
lers system manual
(https://support.industry.siemens.
com/cs/ww/en/view/90885010)
21