Siemens SIMATIC ET 200S Function Manual - Page 35

Browse online or download pdf Function Manual for Industrial Equipment Siemens SIMATIC ET 200S. Siemens SIMATIC ET 200S 40 pages. Distributed i/o digital electronic module 4do dc24v/2a hf
Also for Siemens SIMATIC ET 200S: Operator's Manual (18 pages), Manual (16 pages), User Manual (16 pages), User Manual (26 pages), Manual (37 pages), Manual (24 pages), Operating Instructions (4 pages), Original Operating Instructions (19 pages), Original Operating Instructions (20 pages), Manual (34 pages), Manual (14 pages), Manual (24 pages), Original Operating Instructions (17 pages), Original Operating Instructions (19 pages), Manual (16 pages), Manual (28 pages), Manual (12 pages), Manual (32 pages), Manual (18 pages), Manual (12 pages), Manual (28 pages), Manual (22 pages), Manual (22 pages), Manual (36 pages), Manual (16 pages)

Siemens SIMATIC ET 200S Function Manual
For a more detailed description, refer to the section titled "Diagnostics and monitoring
functions" in the SIMATIC
Edition).
Responses to a diagnostic alarm
If a diagnostic alarm is issued, the following occurs:
1. The group error LED (SF) lights up on the ET 200S frequency converter.
2. Diagnostic data is written to the TSI#details variable in the Taskstartinfo of
PeripheralFaultTask. The program assigned to the PeripheralFaultTask is executed.
3. The SIMOTION device goes into STOP mode if a program has not been assigned to the
PeripheralFaultTask.
4. The group error LED (SF) goes out as soon as the error has been remedied.
Bit assignment
The TS#details variable is assigned in the same way as in a SIMATIC system.
Note
For a more detailed description, refer to the section titled "Diagnostics and monitoring
functions" in the SIMATIC
Edition).
Supplement for the ET 200S frequency converter
Function Manual, 01/2015
ET 200S FC Frequency Converter Operating Instructions (03/2005
ET 200S FC Frequency Converter Operating Instructions (03/2005
Alarm processing
6.2 Diagnostic alarms
35