Siemens SIMATIC ET 200S Manual - Page 10

Browse online or download pdf Manual for Industrial Equipment Siemens SIMATIC ET 200S. Siemens SIMATIC ET 200S 24 pages. Distributed i/o digital electronic module 4do dc24v/2a hf
Also for Siemens SIMATIC ET 200S: Operator's Manual (18 pages), Manual (16 pages), User Manual (16 pages), User Manual (26 pages), Manual (37 pages), Manual (24 pages), Function Manual (40 pages), Operating Instructions (4 pages), Original Operating Instructions (19 pages), Original Operating Instructions (20 pages), Manual (34 pages), Manual (14 pages), Original Operating Instructions (17 pages), Original Operating Instructions (19 pages), Manual (16 pages), Manual (28 pages), Manual (12 pages), Manual (32 pages), Manual (18 pages), Manual (12 pages), Manual (28 pages), Manual (22 pages), Manual (22 pages), Manual (36 pages), Manual (16 pages)

Siemens SIMATIC ET 200S Manual
Properties
1.1 2AI I 4WIRE ST analog electronic module (6ES7134-4GB11-0AB0)
Noise suppression for f = n x (f1 ± 1%),
(f1 = interference frequency)
Crosstalk between the inputs
Operational limit (in the entire temperature range,
with reference to the input range)
Basic error limit (operational limit at 25°C with
reference to input range)
Temperature error (with reference to the input
range)
Linearity error (with reference to the input range)
Repeatability
(in steady state at 25°C with reference to input
range)
Input range (rated value)/input resistance
Permitted input current (destruction limit)
Smoothing of the measured values
10
Common mode interference
(peak value of interference < rated value of
input range)
Current
Suppression of interference, limits of error
Min. 70 dB
Min. - 50 dB
± 0,6 %
± 0,4 %
± 0.005 %/K
± 0,01 %
± 0,05 %
Data for selecting a sensor
± 20 mA/50 Ω
4 to 20 mA/50 Ω
40 mA
Yes, can be assigned parameters in 4 steps by
means of digital filtering
Step
None
Weak
Medium
Strong
2AI I 4WIRE ST analog electronic module (6ES7134-4GB11-0AB0)
Time constant
1 x cycle time
4 x cycle time
32 x cycle time
64 x cycle time
Manual, 04/2007, A5E01076100-01