Also for Siemens SIMATIC ET 200S: Operator's Manual (18 pages), Manual (16 pages), User Manual (16 pages), User Manual (26 pages), Manual (37 pages), Manual (24 pages), Function Manual (40 pages), Operating Instructions (4 pages), Original Operating Instructions (19 pages), Original Operating Instructions (20 pages), Manual (34 pages), Manual (14 pages), Manual (24 pages), Original Operating Instructions (17 pages), Original Operating Instructions (19 pages), Manual (16 pages), Manual (28 pages), Manual (12 pages), Manual (32 pages), Manual (18 pages), Manual (12 pages), Manual (28 pages), Manual (22 pages), Manual (22 pages), Manual (16 pages)

Siemens SIMATIC ET 200S Manual
Using PTC resistors
PTCs are suitable for temperature monitoring and as thermal protective devices for complex
drives and transformer windings.
● Select "Two-wire resistor" and "PTC" at parameter assignment:
● Connect the PTC in accordance with the two-wire connection method.
● Apply PTC resistors of Type A (PTC thermistors) in accordance with DIN / VDE 0660,
● If the diagnosis "Overrun/underrun" is enabled, a diagnosis "Lower limit exceeded"
● Sensor data for the PTC resistor:
Switching points
(TNF-5) °C
(TNF+5) °C
(TNF+15) °C
Measuring voltage
Voltage on the PTC
2AI RTD HF analog electronic module (6ES7134-4NB51-0AB0)
Manual, 05/2007, A5E01076876-02
Part 302.
indicating a short-circuit is indicated at resistance values < 18 Ω.
Properties
specifications
Behavior with rising temperature
< 550 Ω
550 Ω to 1650 Ω
> 1650 Ω
Behavior with falling temperature
> 750 Ω
750 Ω to 540 Ω
< 540 Ω
Max. 550 Ω
Min. 1330 kΩ
Min. 4000 kΩ
Max. 7.5 V
1.1 2AI RTD HF analog electronic module (6ES7134-4NB51-0AB0)
Technical
Normal range:
SIMATIC S7: Bit 0 = "0", Bit 2 = "0" (in the PII)
SIMATIC S5: Bit 3 = "0", Bit 5 = "0" (in the PII)
Prewarning range:
SIMATIC S7: Bit 0 = "0", Bit 2 = "1" (in the PII)
SIMATIC S5: Bit 3 = "0", Bit 5 = "1" (in the PII)
Addressable range:
SIMATIC S7: Bit 0 = "1", Bit 2 = "0" (in the PII)
SIMATIC S5: Bit 3 = "1", Bit 5 = "0" (in the PII)
Addressable range:
SIMATIC S7: Bit 0 = "1", Bit 2 = "0" (in the PII)
SIMATIC S5: Bit 3 = "1", Bit 5 = "0" (in the PII)
Prewarning range:
SIMATIC S7: Bit 0 = "0", Bit 2 = "1" (in the PII)
SIMATIC S5: Bit 3 = "0", Bit 5 = "1" (in the PII)
Normal range:
SIMATIC S7: Bit 0 = "0", Bit 2 = "0" (in the PII)
SIMATIC S5: Bit 3 = "0", Bit 5 = "0" (in the PII)
TNF= rated operating temperature
Properties
Remarks
13