Siemens SIMATIC ET 200SP Product Information - Page 36

Browse online or download pdf Product Information for Industrial Equipment Siemens SIMATIC ET 200SP. Siemens SIMATIC ET 200SP 38 pages. Distributed i/o system
Also for Siemens SIMATIC ET 200SP: Manual (40 pages), User Manual (21 pages), Manual (34 pages), Manual (48 pages), Manual (30 pages), Manual (34 pages), Manual (37 pages), Manual (36 pages), Manual (44 pages), Manual (31 pages), Manual (35 pages), Manual (23 pages), Configuration Manual (20 pages), Manual (34 pages), Manual (29 pages), Manual (33 pages), Manual (31 pages), User Manual (32 pages), Manual (31 pages), Manual (28 pages), Manual (41 pages), Manual (32 pages), Manual (49 pages), Manual (24 pages), Manual (34 pages), Manual (41 pages), Manual (30 pages), Manual (31 pages), Manual (27 pages), Manual (24 pages), Manual (24 pages), Manual (25 pages), Manual (49 pages), Manual (40 pages), Manual (38 pages), Manual (39 pages), Product Information (24 pages), Manual (32 pages), Product Information (10 pages), Equipment Manual (43 pages), Manual (33 pages), Equipment Manual (44 pages), Original Operating Instructions (6 pages), Manual (35 pages), Manual (28 pages), Equipment Manual (32 pages), Manual (50 pages), Manual (30 pages), Manual (26 pages), Manual (28 pages), Manual (34 pages), Manual (44 pages), Manual (33 pages), Equipment Manual (42 pages), Original Instructions Manual (16 pages)

Siemens SIMATIC ET 200SP Product Information
Glossary
Safety class
Safety level (Safety Integrity Level) SIL according to IEC 61508:2010. The higher the Safety
Integrity Level, the more rigid the measures for prevention of systematic faults and for
management of systematic faults and hardware failures.
The fail-safe modules support operation in safety mode up to safety class SIL3.
Safety function
A mechanism integrated in the → F-CPU and → F-I/O that enables their use in → the fail-safe
system SIMATIC Safety.
According to IEC 61508:2010 A safety function is implemented by a safety system in order to
maintain or force a system safe state in the event of a specific fault.
Safety message frame
In safety mode, data are transferred between the → F-CPU and → F-I/O in a safety message
frame.
Safety mode
Operating mode of → F-I/O that enables → safety-related communication via → safety
message frames.
→ ET 200SP fail-safe modules can only used in safety mode.
Safety program
Safety-related user program
Safety-related communication
Communication used to exchange fail-safe data.
Sensor evaluation
There are two types of sensor evaluation:
→ 1oo1 evaluation – sensor signal is read once
→ 1oo2 evaluation – sensor signal is read in twice by the same F-module and compared
internally
Sensors
Sensors are used for accurate detection of digital and analog signals as well as routes,
positions, velocities, rotational speeds, masses, etc.
36
ET 200SP distributed I/O system
Product Information, 07/2013, A5E32288220-AA