Also for Siemens SIMATIC ET 200SP: Manual (40 pages), User Manual (21 pages), Manual (34 pages), Manual (48 pages), Manual (30 pages), Manual (34 pages), Product Information (38 pages), Manual (36 pages), Manual (44 pages), Manual (31 pages), Manual (35 pages), Manual (23 pages), Configuration Manual (20 pages), Manual (34 pages), Manual (29 pages), Manual (33 pages), Manual (31 pages), User Manual (32 pages), Manual (31 pages), Manual (28 pages), Manual (41 pages), Manual (32 pages), Manual (49 pages), Manual (24 pages), Manual (34 pages), Manual (41 pages), Manual (30 pages), Manual (31 pages), Manual (27 pages), Manual (24 pages), Manual (24 pages), Manual (25 pages), Manual (49 pages), Manual (40 pages), Manual (38 pages), Manual (39 pages), Product Information (24 pages), Manual (32 pages), Product Information (10 pages), Equipment Manual (43 pages), Manual (33 pages), Equipment Manual (44 pages), Original Operating Instructions (6 pages), Manual (35 pages), Manual (28 pages), Equipment Manual (32 pages), Manual (50 pages), Manual (30 pages), Manual (26 pages), Manual (28 pages), Manual (34 pages), Manual (44 pages), Manual (33 pages), Equipment Manual (42 pages), Original Instructions Manual (16 pages)

Siemens SIMATIC ET 200SP Manual
Parameters/address space

4.4 Address space

4.4
Address space
Configuration options of the DI 8×NAMUR HF
Configuration with value status:
● DI 8×NAMUR HF QI
Evaluating the value status
As a result of configuration with value status (QI), an additional byte is allocated in the input
address space. Each bit in this byte is assigned to a channel and returns information about
the validity of the digital value.
Deactivated channels or channels that are not operating correctly return a value status
of QI = 0.
With changeover contacts, the value status of a normally closed contact channel is always
QI = 0. The validity of the signal must be checked on the normally open contact channel.
Address space of the digital input module DI 8×NAMUR HF
The following figure shows the assignment of address space for the DI 8×NAMUR HF with
value status (Quality Information (QI)).
Figure 4-2
Technology functions
All technology functions, such as
● Pulse stretching
● Chatter monitoring
● Changeover error
● Hardware interrupt
require a valid input signal that returns QI = 1 (no diagnostics detected). Otherwise, they will
not run.
18
Address space of the DI 8×NAMUR HF digital input module with value status
DI 8xNAMUR HF digital input module (6ES7131-6TF00-0CA0)
Manual, 02/2014, A5E03894478-01