Also for Siemens SIMATIC ET 200SP: Manual (40 pages), User Manual (21 pages), Manual (34 pages), Manual (48 pages), Manual (30 pages), Manual (34 pages), Product Information (38 pages), Manual (37 pages), Manual (36 pages), Manual (44 pages), Manual (31 pages), Manual (35 pages), Configuration Manual (20 pages), Manual (34 pages), Manual (29 pages), Manual (33 pages), Manual (31 pages), User Manual (32 pages), Manual (31 pages), Manual (28 pages), Manual (41 pages), Manual (32 pages), Manual (49 pages), Manual (24 pages), Manual (34 pages), Manual (41 pages), Manual (30 pages), Manual (31 pages), Manual (27 pages), Manual (24 pages), Manual (24 pages), Manual (25 pages), Manual (49 pages), Manual (40 pages), Manual (38 pages), Manual (39 pages), Product Information (24 pages), Manual (32 pages), Product Information (10 pages), Equipment Manual (43 pages), Manual (33 pages), Equipment Manual (44 pages), Original Operating Instructions (6 pages), Manual (35 pages), Manual (28 pages), Equipment Manual (32 pages), Manual (50 pages), Manual (30 pages), Manual (26 pages), Manual (28 pages), Manual (34 pages), Manual (44 pages), Manual (33 pages), Equipment Manual (42 pages), Original Instructions Manual (16 pages)

Siemens SIMATIC ET 200SP Manual

Wiring

3.1

Wiring and block diagram

This section includes the block diagram of the DQ 4x24..230VAC/2A ST module with the
terminal assignments for 2-wire and 3-wire connection.
You can find information on wiring the BaseUnit in the ET 200SP distributed I/O system
system manual.
NOTICE
Dangerous voltage. Risk of death or serious injury.
Always disconnect the system and module from the power supply before commencing
work.
Note
Limiting overvoltage
You must ensure overvoltage is limited to 1 kV for the encoder supply.
Note
Power limitation
To limit power, each input voltage must have a fuse with a maximum rating of 10 A tripping
current. The fuse must be a quick-acting microfuse.
Note
You may use and combine the different wiring options for all channels.
10
DQ 4x24..230VAC/2A ST digital output module (6ES7132-6FD00-0BB1)
3