Also for Siemens SIMATIC ET 200SP: Manual (40 pages), User Manual (21 pages), Manual (34 pages), Manual (48 pages), Manual (30 pages), Manual (34 pages), Product Information (38 pages), Manual (37 pages), Manual (36 pages), Manual (44 pages), Manual (31 pages), Manual (35 pages), Manual (23 pages), Configuration Manual (20 pages), Manual (34 pages), Manual (29 pages), Manual (33 pages), Manual (31 pages), User Manual (32 pages), Manual (31 pages), Manual (28 pages), Manual (41 pages), Manual (49 pages), Manual (24 pages), Manual (34 pages), Manual (41 pages), Manual (30 pages), Manual (31 pages), Manual (27 pages), Manual (24 pages), Manual (24 pages), Manual (25 pages), Manual (49 pages), Manual (40 pages), Manual (38 pages), Manual (39 pages), Product Information (24 pages), Manual (32 pages), Product Information (10 pages), Equipment Manual (43 pages), Manual (33 pages), Equipment Manual (44 pages), Original Operating Instructions (6 pages), Manual (35 pages), Manual (28 pages), Equipment Manual (32 pages), Manual (50 pages), Manual (30 pages), Manual (26 pages), Manual (28 pages), Manual (34 pages), Manual (44 pages), Manual (33 pages), Equipment Manual (42 pages), Original Instructions Manual (16 pages)

Siemens SIMATIC ET 200SP Manual

Parameters/address space

4.1

Parameters

Parameters for RQ 4x120VDC-230VAC/5A NO ST
Specify the module properties with the various parameters in the course of your STEP 7
configuration. The following table lists the configurable parameters. The effective range of
the parameters depends on the type of configuration.
The following configurations are possible:
● Central operation with an ET 200SP CPU
● Distributed operation on PROFINET IO in an ET 200SP system
● Distributed operation with PROFIBUS DP in an ET 200SP system
When assigning parameters in the user program, use the "WRREC" instruction to transfer
the parameters to the module using the data records; refer to the section Parameter
assignment and structure of the parameter data record (Page 29).
The following parameter settings are possible:
Table 4- 1
Settable parameters and their defaults (GSD file)
Parameter
Diagnostics
No supply voltage L+
Channel enabled
Reaction to CPU STOP •
Due to the limited number of parameters at a maximum of 244 bytes per ET 200SP station with a PROFIBUS GSD
1
configuration, the configuration options are restricted. If required, you can assign these parameters using data rec-
ord 128 as described in the "GSD file PROFINET IO" column (see table above). The parameter length of the I/O module
is 8 bytes.
Digital output module RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD01-0BB1)
Manual, 09/2017, A5E03576775-AE
Value range
Disable
Enable
Disable
Enable
Turn off
Keep last value
Output substitute value 1
Default
Configura-
tion in RUN
Disable
yes
Enable
yes
Turn off
yes
Scope with configuration software,
e.g. STEP 7 (TIA Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS DP
Module
Module
Channel
Channel
Channel
Module
4
1
17