Siemens SIMATIC ET 200SP Manual - Page 12

Browse online or download pdf Manual for Industrial Equipment Siemens SIMATIC ET 200SP. Siemens SIMATIC ET 200SP 49 pages. Distributed i/o system
Also for Siemens SIMATIC ET 200SP: Manual (40 pages), User Manual (21 pages), Manual (34 pages), Manual (48 pages), Manual (30 pages), Manual (34 pages), Product Information (38 pages), Manual (37 pages), Manual (36 pages), Manual (44 pages), Manual (31 pages), Manual (35 pages), Manual (23 pages), Configuration Manual (20 pages), Manual (34 pages), Manual (29 pages), Manual (33 pages), Manual (31 pages), User Manual (32 pages), Manual (31 pages), Manual (28 pages), Manual (41 pages), Manual (32 pages), Manual (49 pages), Manual (24 pages), Manual (34 pages), Manual (41 pages), Manual (30 pages), Manual (31 pages), Manual (27 pages), Manual (24 pages), Manual (24 pages), Manual (25 pages), Manual (40 pages), Manual (38 pages), Manual (39 pages), Product Information (24 pages), Manual (32 pages), Product Information (10 pages), Equipment Manual (43 pages), Manual (33 pages), Equipment Manual (44 pages), Original Operating Instructions (6 pages), Manual (35 pages), Manual (28 pages), Equipment Manual (32 pages), Manual (50 pages), Manual (30 pages), Manual (26 pages), Manual (28 pages), Manual (34 pages), Manual (44 pages), Manual (33 pages), Equipment Manual (42 pages), Original Instructions Manual (16 pages)

Siemens SIMATIC ET 200SP Manual
Properties
The module has the following technical properties:
● Analog input module with 2 inputs
● Measurement types voltage and current for 2-/4-wire transducers
● Input ranges for voltage measurement:
– ±10 V, resolution 16 bit including sign
– ±5 V, resolution 15 bit incl. sign
– 1 to 5 V, resolution 13 bit
– 0 to 10 V, resolution 15 bit
● Input ranges for current measurement:
– ±20 mA, resolution 16 bit incl. sign
– 4 to 20 mA, resolution 14 bit
– 0 to 20 mA, resolution 15 bit
● Electrically isolated between the channels
● Electrically isolated from supply voltage L+
● Permitted common mode voltage: 100 V
● Configurable diagnostics (per channel)
● Hardware interrupt on limit violation can be set per channel (two high and two low limits
per channel)
The module supports the following functions:
● Firmware update
● I&M identification data
● Reconfiguration in RUN
● PROFIenergy
Table 2- 1
Basic version
Isochronous mode with send clock up to 250 µs
Value status
Oversampling channel 0
Oversampling channel 0 and 1
Isochronous mode with send clock up to 125 µs
Analog input module AI 2xU/I 2-/4-wire HS (6ES7134-6HB00-0DA1)
Manual, 09/2018, A5E03576060-AF
Version dependencies of other module functions
Function
/35 V
pp
rms
Product version of
the module as of
1
2
2
2
2
2
Product overview
2.1 Properties
Firmware version of
the module as of
V1.0.0
V1.1.0
V1.1.0
V1.1.0
V2.0.0
V2.0.1
11