Siemens SIMATIC ET 200SP Manual - Page 36

Browse online or download pdf Manual for Industrial Equipment Siemens SIMATIC ET 200SP. Siemens SIMATIC ET 200SP 49 pages. Distributed i/o system
Also for Siemens SIMATIC ET 200SP: Manual (40 pages), User Manual (21 pages), Manual (34 pages), Manual (48 pages), Manual (30 pages), Manual (34 pages), Product Information (38 pages), Manual (37 pages), Manual (36 pages), Manual (44 pages), Manual (31 pages), Manual (35 pages), Manual (23 pages), Configuration Manual (20 pages), Manual (34 pages), Manual (29 pages), Manual (33 pages), Manual (31 pages), User Manual (32 pages), Manual (31 pages), Manual (28 pages), Manual (41 pages), Manual (32 pages), Manual (49 pages), Manual (24 pages), Manual (34 pages), Manual (41 pages), Manual (30 pages), Manual (31 pages), Manual (27 pages), Manual (24 pages), Manual (24 pages), Manual (25 pages), Manual (40 pages), Manual (38 pages), Manual (39 pages), Product Information (24 pages), Manual (32 pages), Product Information (10 pages), Equipment Manual (43 pages), Manual (33 pages), Equipment Manual (44 pages), Original Operating Instructions (6 pages), Manual (35 pages), Manual (28 pages), Equipment Manual (32 pages), Manual (50 pages), Manual (30 pages), Manual (26 pages), Manual (28 pages), Manual (34 pages), Manual (44 pages), Manual (33 pages), Equipment Manual (42 pages), Original Instructions Manual (16 pages)

Siemens SIMATIC ET 200SP Manual
Article number
Encoder
Connection of signal encoders
for voltage measurement
for current measurement as 2-wire trans-
ducer
Burden of 2-wire transmitter, max.
for current measurement as 4-wire trans-
ducer
Errors/accuracies
Linearity error (relative to input range), (+/-)
Temperature error (relative to input range), (+/-
)
Crosstalk between the inputs, min.
Repeat accuracy in steady state at 25 °C (rela-
tive to input range), (+/-)
Operational error limit in overall temperature ran-
ge
Voltage, relative to input range, (+/-)
Current, relative to input range, (+/-)
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)
Current, relative to input range, (+/-)
Interference voltage suppression for f = n x (f1 +/-
1 %), f1 = interference frequency
Common mode voltage, max.
Common mode interference, min.
Isochronous mode
Isochronous operation (application synchro-
nized up to terminal)
Filtering and processing time (TCI), min.
Bus cycle time (TDP), min.
Interrupts/diagnostics/status information
Alarms
Diagnostic alarm
Limit value alarm
Analog input module AI 2xU/I 2-/4-wire HS (6ES7134-6HB00-0DA1)
Manual, 09/2018, A5E03576060-AF
6ES7134-6HB00-0DA1
Yes
Yes
650 Ω
Yes
0.03 %
0.01 %/K
-50 dB
0.1 %
0.3 %
0.3 %
0.2 %
0.2 %
35 V
90 dB
Yes
80 µs
125 µs; Starting from firmware Version V2.0.1
Yes
Yes; two upper and two lower limit values in each
case
Technical specifications
6.1 Technical specifications
35