Also for Siemens SIMATIC ET 200SP: Manual (40 pages), User Manual (21 pages), Manual (34 pages), Manual (48 pages), Manual (30 pages), Manual (34 pages), Product Information (38 pages), Manual (37 pages), Manual (36 pages), Manual (44 pages), Manual (31 pages), Manual (35 pages), Manual (23 pages), Configuration Manual (20 pages), Manual (34 pages), Manual (29 pages), Manual (33 pages), Manual (31 pages), User Manual (32 pages), Manual (31 pages), Manual (28 pages), Manual (41 pages), Manual (32 pages), Manual (49 pages), Manual (24 pages), Manual (34 pages), Manual (41 pages), Manual (30 pages), Manual (31 pages), Manual (27 pages), Manual (24 pages), Manual (24 pages), Manual (25 pages), Manual (49 pages), Manual (38 pages), Manual (39 pages), Product Information (24 pages), Manual (32 pages), Product Information (10 pages), Equipment Manual (43 pages), Manual (33 pages), Equipment Manual (44 pages), Original Operating Instructions (6 pages), Manual (35 pages), Manual (28 pages), Equipment Manual (32 pages), Manual (50 pages), Manual (30 pages), Manual (26 pages), Manual (28 pages), Manual (34 pages), Manual (44 pages), Manual (33 pages), Equipment Manual (42 pages), Original Instructions Manual (16 pages)

Siemens SIMATIC ET 200SP Manual
5.2

Diagnostic alarms

For each diagnostics event, a diagnostic alarm is issued and the DIAG LED flashes red on
the communication module. You can read out the diagnostics alarms, for example, in the
diagnostics buffer of the CPU. You can evaluate the error codes with the user program.
Table 5- 6
Error types
Diagnostic alarm
Error
code
Short-circuit
1
H
Undervoltage
2
H
Overvoltage
3
H
Overheating
5
H
Wire break
6
H
Overflow
7
H
Underflow
8
H
Error
9
H
Configuration
10
H
error
Supply voltage
11
H
missing
Defective fuse
12
H
Safety shutdown
19
H
External fault
1A
H
Communication module IO-Link Master CM 4xIO-Link (6ES7137-6BD00-0BA0)
Manual, 10/2017, A5E03856846-AD
Meaning (IO-Link error code)
Short-circuit in the process cables on the IO-Link device (1804
Short-circuit on IO device (7710
Supply voltage too low (5111
Supply voltage too high (5110
Temperature exceeded on master (1805
Temperature exceeded on device (4000
No IO-Link device connected
There is a break in the signal line to the IO-Link device
IO-Link device cannot communicate due to another error (1800
Process tag range exceeded (8C10
Measuring range exceeded (8C20
Process tag range too low (8C30
All IO-Link error codes which are not listed here are mapped to
this PROFIBUS DP error
Incorrect device (1802
Vendor ID and Device ID not defined (1817
Process data length of the IO-Link device exceeded (1818
No cycle time configured (1819
Cannot configure IO-Link master (1882
Storage error (1886
)
H
Process data length exceeded (1887
PQI not supported (1889
Device was not configured correctly (6320
L+ supply voltage for device missing (1806
L+ supply voltage for device too low (<20 V) (1807
Fuse on device is defective (5101
Serious error (master has to be replaced) (1880
Error in data storage (1809
More than 6 errors are pending simultaneously on the IO-Link
device (1808
)
H
Consistency error in electronic coding element (1885
Process data length exceeded (1887
)
H
, 5112
)
H
H
)
H
)
H
, 4210
H
H
)
H
)
H
)
H
)
H
)
H
)
H
, 1883
)
H
H
)
H
)
H
, 6321
H
)
H
)
H
H
, 180A
, 180B
, 180C
H
H
H
)
H
Diagnostic alarms
5.2 Diagnostic alarms
IO-Link
master
X
)
H
X
)
X
)
H
X
)
H
, 6350
)
H
H
X
)
H
X
)
X
, 180D
)
H
H
)
H
IO-Link
device
X
X
X
X
X
X
X
X
X
31