Siemens SIMATIC ET 200SP Manual - Page 28

Browse online or download pdf Manual for Industrial Equipment Siemens SIMATIC ET 200SP. Siemens SIMATIC ET 200SP 32 pages. Distributed i/o system
Also for Siemens SIMATIC ET 200SP: Manual (40 pages), User Manual (21 pages), Manual (34 pages), Manual (48 pages), Manual (30 pages), Manual (34 pages), Product Information (38 pages), Manual (37 pages), Manual (36 pages), Manual (44 pages), Manual (31 pages), Manual (35 pages), Manual (23 pages), Configuration Manual (20 pages), Manual (34 pages), Manual (29 pages), Manual (33 pages), Manual (31 pages), User Manual (32 pages), Manual (31 pages), Manual (28 pages), Manual (41 pages), Manual (32 pages), Manual (49 pages), Manual (24 pages), Manual (34 pages), Manual (41 pages), Manual (30 pages), Manual (31 pages), Manual (27 pages), Manual (24 pages), Manual (24 pages), Manual (25 pages), Manual (49 pages), Manual (40 pages), Manual (38 pages), Manual (39 pages), Product Information (24 pages), Product Information (10 pages), Equipment Manual (43 pages), Manual (33 pages), Equipment Manual (44 pages), Original Operating Instructions (6 pages), Manual (35 pages), Manual (28 pages), Equipment Manual (32 pages), Manual (50 pages), Manual (30 pages), Manual (26 pages), Manual (28 pages), Manual (34 pages), Manual (44 pages), Manual (33 pages), Equipment Manual (42 pages), Original Instructions Manual (16 pages)

Siemens SIMATIC ET 200SP Manual

Configuring

Introduction
The mixed configuration allows the connection of up to 16 ET 200AL I/O modules to the
ET 200SP via ET-Connection. The figure below shows the configuration of the ET-Connection
and the assignment of the slots.
ET 200SP I/O modules
ET 200SP server module
Slots
PROFINET IO
Figure 7-1
Mixed configuration
For more information about connecting ET-Connection, supply voltages, actuators and
sensors, refer to the ET 200AL system manual.
Configuration with a CPU
In a configuration with a CPU, a maximum of 2 slots can be used immediately to the right of
the CPU with CM DP module or Ethernet CP. Combinations are also possible, i.e. CM DP
module and one Ethernet CP or two Ethernet CPs.
BU-Send and BA-Send should always be inserted to the immediate right of the CM/CP.
Mixed configuration
Equipment Manual, 11/2020, A5E33344611-AD
1st ET 200AL I/O module
16th ET 200AL I/O module
ET-Connection
7
27