Siemens SIMATIC ET 200SP Manual - Page 26

Browse online or download pdf Manual for Industrial Equipment Siemens SIMATIC ET 200SP. Siemens SIMATIC ET 200SP 44 pages. Distributed i/o system
Also for Siemens SIMATIC ET 200SP: Manual (40 pages), User Manual (21 pages), Manual (34 pages), Manual (48 pages), Manual (30 pages), Manual (34 pages), Product Information (38 pages), Manual (37 pages), Manual (36 pages), Manual (44 pages), Manual (31 pages), Manual (35 pages), Manual (23 pages), Configuration Manual (20 pages), Manual (34 pages), Manual (29 pages), Manual (33 pages), Manual (31 pages), User Manual (32 pages), Manual (31 pages), Manual (28 pages), Manual (41 pages), Manual (32 pages), Manual (49 pages), Manual (24 pages), Manual (34 pages), Manual (41 pages), Manual (30 pages), Manual (31 pages), Manual (27 pages), Manual (24 pages), Manual (24 pages), Manual (25 pages), Manual (49 pages), Manual (40 pages), Manual (38 pages), Manual (39 pages), Product Information (24 pages), Manual (32 pages), Product Information (10 pages), Equipment Manual (43 pages), Manual (33 pages), Equipment Manual (44 pages), Original Operating Instructions (6 pages), Manual (35 pages), Manual (28 pages), Equipment Manual (32 pages), Manual (50 pages), Manual (30 pages), Manual (26 pages), Manual (28 pages), Manual (34 pages), Manual (33 pages), Equipment Manual (42 pages), Original Instructions Manual (16 pages)

Siemens SIMATIC ET 200SP Manual
Interrupts, diagnostics, error, and system messages
5.1 Status and error displays
PWR LED on the interface module
Table 5- 2
PWR status display on the interface module
PWR LED
Supply voltage not present or too small
Off
Supply voltage present
On
LK1/LK2 LED on the BusAdapter
Table 5- 3
LK1/LK2status display on the BusAdapter
LEDs LK1/LK2
There is no Ethernet connection between the
PROFINET IO interface of your PROFINET device
Off
and a communication partner (e.g. IO controller).
There is an Ethernet connection between the
PROFINET IO interface of your PROFINET device
On
and a communication partner (e.g. IO controller).
The "Node flash test" is run (the RN/ER/MT LEDs
also flash).
Flashes
LED display of configuration errors
Configuration errors of the ET 200SP distributed I/O system are output on the
interface
 m odule by the ERROR (red) and MAINT (yellow) LEDs.
The following configuration errors are indicated by the LEDs:
● More than one I/O module pulled
● Missing server module
● Interruptions or short circuit on the backplane bus
26
Meaning
Meaning
Remedy
Check the supply voltage.
-
Remedy
Check whether the bus cable to the switch/
IO controller is interrupted.
-
-
IM 155-6 PN ST interface module (6ES7155-6AU00-0BN0)
Manual, 12/2014, A5E03576904-AC