Siemens SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA Manual - Page 32
Browse online or download pdf Manual for Industrial Equipment Siemens SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA. Siemens SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA 38 pages. Digital output module
Also for Siemens SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA: Equipment Manual (36 pages)
Drivers, parameters, diagnostics messages and address space
A.2 Parameters, diagnostics messages and address space without PCS 7
Error_
Error_
Code_1
Code_2
0xE0
0x02
0xE1
0x01
0xE1
0x06
0xE1
0x0E
A.2.2
Parameter assignment and structure of the module/channel parameters
Structure of data record 128
Data record 128 has a length of 76 bytes.
It contains the channel parameters of the 32 channels.
Figure A-1
32
Cause
Header error (number or length of parameter
block)
Reserved bit set
Invalid encoding for substitute value reaction
Invalid redundancy parameter assignment
Structure of data record 128
Remedy
Correct the length and number of the param‐
eter blocks.
Check and correct the parameters
Digital output module DQ 32x24VDC/0.5A HA (6DL1132-6BL00-0PH1)
Manual, 09/2018, A5E39265993-AA