Also for Siemens SIMATIC NET: Operating Instructions Manual (29 pages), Operating Instructions Manual (50 pages), Operating Instructions Manual (28 pages), Assembly Instructions Manual (6 pages), Product Information (6 pages), Installation Manual (40 pages), Installation Manual (40 pages), Reference Manual (14 pages), Installation Manual (34 pages), Installation Manual (48 pages), Operating Instructions Manual (32 pages)

Siemens SIMATIC NET Installation Manual
EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RS900F meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper ports. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
Fast Transient
Dielectric Strength
Environmental Type Tests
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
RUGGEDCOM RS900F
Installation Manual, 04/2021, C79000-G8976-1350-07
Description
ESD
Radiated RFI
Oscillatory
HV Impulse
Test
Cold Temperature
Dry Heat
Humidity (Damp
Heat, Cyclic)
6.2 EMC and Environmental Type Tests
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Description
Test Ad
Test Bd
Test Db
Vibration
Shock
Certification
Test Levels
± 8 kV
± 15 kV
35 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
2.5 kV Common Mode @ 1 MHz
2.5 kV Common and
Differential Mode @ 1 MHz
2.5 kV Common and
Differential Mode @ 1 MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kV (Failsafe Relay)
1.5 kV
2 kV
Test Levels
Severity Levels
-40 °C (-40
°F), 16 Hours
85 °C (185
°F), 16 Hours
95% (Non-
Condensing),
55 °C (131
°F), 6 Cycles
2 g @ 10 to 150 Hz
30 g @ 11 ms
 
 
 
Class 2
Class 2
39